background image

 

 

 

 

 

NFO

 

Drives

 

AB

 

2021

 

 

201013

2

 

Operating

 

and

 

Installation

 

Manual

 

 

42

 

whatever setpoint is available from the terminals (e.g. analog input, selected fix frequencies, etc), and for run 
command 101h the setpoint is taken from Input Frequency Setpoint register (when in Frequency mode), or Input 
Speed Setpoint register (when in Speed mode). 

To setup inverter for automatic stop if communication is lost, it’s possible to use the serial timeout parameter, see 
corresponding paragraph in section 5. 

Status from inverter is reported in parameter Inverter status which can be read from Modbus register addresses 
02A4h and 02A5h. Both will reply the same status code, but reading the former will also trigger an acknowledge of 
alarm or fault condition, if such is active. Table below shows code, corresponding text shown on inverter display, 
and a short description. The codes in 

italic

 are merely status, while other codes indicate an alarm or fault condition.  

 

Code

 

Text

 

Description

 

 

Code

 

Text

 

Description

 

0

 

Erased

 

Error

 

log

 

was

 

erased

 

 

32

 

Decel

 

Inverter

 

is

 

decelerating

 

1

 

GND

 

Fail

 

R

 

Ground

 

fail

 

detected

 

during

 

run

 

 

33

 

Ext

 

Stby

 

Inverter

 

is

 

ready

 

for

 

run

 

cmd

 

in

 

Auto

 

mode

 

2

 

AC

 

Fail

 

Mains

 

power

 

error

 

 

34

 

Ext

 

Run

 

Inverter

 

is

 

running

 

in

 

Auto

 

mode

 

3

 

Temp

 

Hi

 

Too

 

high

 

temperature

 

on

 

heat

 

sink

 

 

35

 

Ext

 

Acc

 

Inverter

 

is

 

accelerating

 

in

 

Auto

 

mode

 

4

 

PTC

 

Temp

 

Motor

 

temperature

 

sensor

 

trip

 

 

36

 

Ext

 

Ret

 

Inverter

 

is

 

decelerating

 

in

 

Auto

 

mode

 

5

 

Overload

 

Electronic

 

motor

 

overload

 

trip

 

 

37

 

Bus

 

Stby

 

Inverter

 

is

 

ready

 

for

 

run

 

cmd

 

in

 

Bus

 

mode

 

6

 

Ain

 

Fail

 

Analog

 

input

 

out

 

of

 

range

 

 

38

 

Bus

 

Run

 

Inverter

 

is

 

running

 

in

 

Bus

 

mode

 

7

 

DC

 

Low

 

Internal

 

undervoltage

 

warning

 

 

39

 

Bus

 

Acc

 

Inverter

 

is

 

accelerating

 

in

 

Bus

 

mode

 

8

 

DC

 

High

 

Internal

 

overvoltage

 

warning

 

and

 

trip

 

 

40

 

Bus

 

Ret

 

Inverter

 

is

 

decelerating

 

in

 

Bus

 

mode

 

9

 

GND

 

Fail

 

S

 

Ground

 

fail

 

detected

 

during

 

stop

 

 

41

 

PI

 

Reg

 

Process

 

regulator

 

is

 

activated

 

at

 

terminal

 

10

 

Imagn

 

Low

 

Magnetization

 

current

 

too

 

low

 

or

 

too

 

high

 

 

42

 

Calibrating

 

Calibrate

 

procedure

 

is

 

ongoing

 

11

 

Cur

 

Low

 

Output

 

current

 

too

 

low

 

 

43

 

Calibr

 

Done

 

Calibrate

 

procedure

 

finished

 

12

 

Cur

 

High

 

Output

 

current

 

too

 

high

 

 

44

 

BasicTun

 

Ok

 

Basic

 

tuning

 

finished

 

13

 

Run

 

Fail

 

Locked

 

rotor

 

/

 

unable

 

to

 

control

 

motor

 

 

45

 

Full

 

Tun

 

Ok

 

Full

 

tuning

 

finished

 

14

 

Sio

 

Fail

 

Serial

 

communication

 

timeout

 

 

46

 

RsMeas

 

Ok

 

Stator

 

resistance

 

measurement

 

finished

 

15

 

Bus

 

Fail

 

Fieldbus

 

communication

 

timeout

 

 

47

 

ParCalc

 

Ok

 

Parameter

 

calculation

 

finished

 

16

 

Tun

 

Fail

 

P

 

Tuning

 

error,

 

parameter

 

value

 

 

48

 

Short

 

Circ

 

Short

 

circuit

 

error

 

detected

 

17

 

Tun

 

Fail

 

M

 

Tuning

 

error,

 

measurement

 

 

49

 

DC

 

Low

 

Trip

 

Internal

 

undervoltage

 

trip

 

18

 

RsMeasFail

 

Tuning

 

error,

 

stator

 

resistance

 

 

50

 

SampleTime

 

Internal

 

error,

 

measurement

 

sample

 

time

 

19

 

TuneCnvFail

 

Tuning

 

error,

 

calculation

 

 

51

 

Motor

 

Volt

 

Voltage

 

detected

 

on

 

motor

 

terminals

 

20

 

Dsp

 

ComErr

 

Internal

 

error,

 

communication

 

 

52

 

Unused

 

Reserved

 

for

 

future

 

use

 

21

 

Cop

 

Restrt

 

Internal

 

error,

 

restart/reboot

 

 

53

 

Not

 

Tuned

 

Tuning

 

has

 

not

 

been

 

performed

 

22

 

Dsp

 

SysErr

 

Internal

 

error,

 

measurement

 

circuits

 

 

54

 

Delay

 

Run

 

Inverter

 

will

 

start

 

after

 

run

 

delay

 

time

 

23

 

Cop

 

ComErr

 

Internal

 

error,

 

communication

 

 

55

 

DC

 

Low

 

Ctrl

 

Internal

 

undervoltage

 

regulation

 

active

 

24

 

Stop

 

Inverter

 

is

 

stopped

 

 

56

 

DC

 

High

 

Ctrl

 

Internal

 

overvoltage

 

regulation

 

active

 

25

 

Wait

 

Inverter

 

is

 

waiting

 

to

 

become

 

ready

 

 

57

 

Fact

 

Reset

 

Parameters

 

was

 

reset

 

to

 

factory

 

default

 

26

 

Brake

 

Ch

 

Brake

 

chopper

 

is

 

operating

 

 

58

 

Cop

 

FwUpdt

 

Firmware

 

update

 

of

 

co

processor

 

27

 

Cur

 

Limit

 

Current

 

limit

 

has

 

been

 

reached

 

 

59

 

Dsp

 

FwUpdt

 

Firmware

 

update

 

of

 

DSP

 

28

 

Tuning

 

Tuning

 

is

 

ongoing

 

 

60

 

Gui

 

FwUpdt

 

Firmware

 

update

 

of

 

GUI

 

29

 

Sleep

 

Inverter

 

has

 

entered

 

sleep

 

mode

 

 

61

 

Unused

 

Reserved

 

for

 

future

 

use

 

30

 

Final

 

Freq

 

Inverter

 

has

 

reached

 

final

 

frequency

 

 

62

 

Unused

 

Reserved

 

for

 

future

 

use

 

31

 

Accel

 

Inverter

 

is

 

accelerating

 

 

63

 

Unused

 

Reserved

 

for

 

future

 

use

 

6.1.3  Control inverter using DriveControl/DriveStatus 

As an alternative to the MODE/SMODE method, it’s also possible to control the inverter in a fashion more similar to 
controlling from Profibus/Profinet, using bit field registers for control and status. When using Drive control register, 
the inverter takes its setpoint from terminals (e.g. analog) or whatever setpoint is selected using other parameters. 

3006469-2022-04

Содержание NFO 3A4D3490D

Страница 1: ...www nfodrives se info nfodrives se 46 454 370 29 Tubba Torg 5 SE 374 32 Karlshamn Sweden Operating and Installation Manual NFO Sinus Optimal 3006469 2022 04...

Страница 2: ...l notes 15 5 2 Keyboard and display 15 5 3 Indicators and Motor status 17 5 4 Operating modes 17 5 4 1 Manual Mode 18 5 4 2 Auto Mode 18 5 4 3 Bus Mode Serial channel Field bus 19 5 5 Parameter specif...

Страница 3: ...elay 2 Run indication 36 5 13 3 Analog outputs 36 5 14 Communication interfaces 36 5 15 Display setup 37 5 16 Status Temperature Counters and Version 37 5 17 Reset to factory settings 37 5 18 Alarm an...

Страница 4: ...l section are connected to the mains supply when the inverter is powered WARNING Touching any components with the mains supply connected can be fatal Always disconnect the mains supply before opening...

Страница 5: ...requency and 100 of rated output current 5 CDM Complete Drive Module efficiency class according to Commission Regulation EU 2019 1781 and IEC 61800 9 2 2017 6 Due to sinusoidal voltage output from the...

Страница 6: ...input PTC or Klixon Electronic motor overload protection Switch off if motor load is over rated power for a long time Ambient conditions Ambient operating temp 10 45 C Storage temp 20 60 C Humidity 0...

Страница 7: ...or cover is not allowed After installation make sure all grommets at the cable entries are mounted and the cover is closed and secured with its screws to avoid contact with dangerous voltages 3 1 Moun...

Страница 8: ...nted between the inverter terminals U V and W and the motor but it must only be operated when the motor is not running First time powered up the installer must select application enter motor name plat...

Страница 9: ...3 2 5 mm AWG 26 AWG 14 To connect the cable carefully push the actuator downward If a tool is used make sure it does not damage any components on the circuit board The signal cables should be fixed to...

Страница 10: ...N Analogue input 2 neg Process regulator actual value input negative 0V I O Ground 24 AOUT1 I Analogue output 1 I Current output 1 25 AOUT1 U Analogue output 1 U Voltage output 1 impedance 50 26 AOUT...

Страница 11: ...ollowing sections Fig 2 Jumper placement and default settings 4 1 3 Analogue current input To use analogue current input 1 move J701 to I position If more than one unit is controlled by a single curre...

Страница 12: ...olled via an RS485 type serial channel Connection is made through terminals 32 RS485 A and 34 RS485 B If the signals are to be bridged to further units terminals 33 and 35 can be used as in Fig 5 Term...

Страница 13: ...r B Brake resistor Connection for external brake resistor between B and Internal DC link voltage negative and positive terminals Positive terminal also used for external brake resistor option PE Prote...

Страница 14: ...A motor with a nominal voltage of 400V Y 230V D must be configured for Y connection and a motor with nominal voltage of 690V Y 400V D must be configured for D connection Setup of motor parameters and...

Страница 15: ...r into parameter or parameter group Save parameter Enter toggle between normal screen and setup menu tree Leave parameter parameter group or leave parameter unsaved Toggle Operating mode between Manua...

Страница 16: ...rating and Installation Manual 16 The following flowchart Fig 9 shows how different screens are reached examples of appearance and explanation of text Fig 9 Programming flowchart and screen examples w...

Страница 17: ...he inverter with an external start signal from terminal 1 DIN1 The Manual mode is normally used for test and programming as well as running the inverter with the use of the keyboard The inverter will...

Страница 18: ...e and run signal terminal 1 DIN1 is not active the Motor status shows Standby The source for the setpoint is selected by the parameter Op Mode Setp Source for the control mode concerned see 5 9 1 5 10...

Страница 19: ...ue Input terminal 0 20 mA Current 0 20mA 20 and 21 J701 at I position 4 20 mA Current 4 20mA 20 and 21 J701 at I position 20 mA Current 20mA 20 and 21 J701 at I position 0 10 V Voltage 0 10V 20 J701 a...

Страница 20: ...lay FixFrq5 FixSpd5 FixReg5 Aout 1 Max RS485 autostop Brake chop Heat sink 3 Menu readonly Start count PTC Temp Tuning DC brake FixFrq6 FixSpd6 FixReg6 Aout 2 Mode RS485 failsafe Stator freq Heat sink...

Страница 21: ...elay from motor has stopped until new Run signal is accepted 0 0 s 0 0 10 0 s Stby Run DC Brake Time in seconds for motor DC braking before start 0 s 0 10 s Stby Run Kp speed Amplifier component speed...

Страница 22: ...0 0 Stby Run Reg On Limit Turn on motor when actual value above on limit 0 0 2000 0 2000 0 Stby Run Output Relay 1 Mode Disable Function disabled Running Motor running Run Fwd Motor running forward Ru...

Страница 23: ...l input current mA Read Keyboard Bitmask input of keyboard Read Terminals Bitmask input of terminals DIN1 8 Read Temperature Motor temp Estimated motor temperature in percent of max Read Power module...

Страница 24: ...ers the installer will be prompted to select application type for the inverter The purpose of selecting application is to preset acceleration and deceleration ramps to a value suitable for the applica...

Страница 25: ...lowable limit for the inverter If the auto tuning process results in an error the cause of error must be identified and corrected before the motor can be started Faults may be due to Motor not connect...

Страница 26: ...has a nominal frequency of 50Hz and is to accelerate from 0 to 80 Hz in 2 sec and brake from 80 to 5 Hz in 9 sec tAccel 50 2 80 1 25 s tDecel 50 9 75 6 00 s The inverter cannot accelerate faster than...

Страница 27: ...the time from when inverter is powered until it accepts a start command PowerOn Delay can be useful to handle short time power failures interrupts and restarting when operating with large inertial to...

Страница 28: ...d motor model Estimated speed ac tual value Integrator c omponent Fig 11 Speed regulator If you have any doubts or problems please contact NFO Drives AB 5 8 8 Frequency sleep setting This function is...

Страница 29: ...max current limit Use the parameters Boost time to set the time after start in seconds and Boost Level 0 100 of exceeding current capacity to set the increased current limit during boost time period...

Страница 30: ...7 Analog 1 F Analogue input 1 clockwise Analog 1 R Analogue input 1 counter clockwise Analog 2 F Analogue input 2 clockwise Analog 2 R Analogue input 2 counter clockwise Fix 1 F Frequency from paramet...

Страница 31: ...rom parameter Fix Spd 4 clockwise Fix 5 F Speed from parameter Fix Spd 5 clockwise Fix 6 F Speed from parameter Fix Spd 6 clockwise Fix 7 F Speed from parameter Fix Spd 7 clockwise Fix 1 R Speed from...

Страница 32: ...al Min och Actual Max which translates the minimum and maximum signal level from the actual value input corresponding to the selected unit The regulator generates an output signal in the form of a set...

Страница 33: ...1 clockwise Analog 1 R Analogue input 1 counter clockwise Analog 2 F Analogue input 2 clockwise Analog 2 R Analogue input 2 counter clockwise Fix 1 F Setpoint from parameter Fix Reg 1 clockwise Fix 2...

Страница 34: ...an be set to 1 a positive or increasing value of the output signal if the regulator setpoint is greater than the current actual value or 1 a negative or decreasing value of the output signal if the re...

Страница 35: ...load The final value of 100 0 corresponds to nominal load and the electronic motor overload protection trips when this value is passed The ambient motor temperature is set with parameter Amb Temp in t...

Страница 36: ...U and terminal 27 AOUT2 U and current output at terminal 24 AOUT1 I and terminal 26 AOUT2 I respectively Both are related to any of the 0V terminals To scale the output use parameter Aout 1 2 Max cur...

Страница 37: ...e selectable actual values are shown lower left middle and right position By default the actual values of IRMS PRMS and PF power factor are shown respectively Users may change these values by altering...

Страница 38: ...g Some faults have to persist for a given time Delay before they generate a fault Motor Fault e g AC fail ErrCnt 2 RstDly RstDly RstDly RstDly T rT ime T rT ime RstDly isreset Fig 14 Typical fault sit...

Страница 39: ...setpoint or Ain Type not set correctly DC Low Trip Fail Fail 2 DC link voltage too low or supply is disconnected Power supply voltage too low Check inverter mains connection DC High Fail Fail 2 DC li...

Страница 40: ...00h to parameter SMODE Modbus register 0298h NFO Classic E00AD 6 Communication using Modbus Modbus RTU or Modbus ASCII can be used for communication with the inverter Available communication ports are...

Страница 41: ...tick per every 36 s Read only Running Time 40 02ACh 02ADh UINT32 h 102 one tick per every 36 s Read only Serial Control Parameters MODE 34 0294h UINT16 1 Manual 2 Auto 3 Bus SMODE Command 35 0298h UIN...

Страница 42: ...nt too low 43 Calibr Done Calibrate procedure finished 12 Cur High Output current too high 44 BasicTun Ok Basic tuning finished 13 Run Fail Locked rotor unable to control motor 45 Full Tun Ok Full tun...

Страница 43: ...re ack 15 Stopping Inverter is decelerating towards a stop An example of communication could be that bus master sets the Bus control command bit and then waits for inverter to respond with Control fro...

Страница 44: ...rter to respond with Enabled Now the bus master may start the motor using the Switch on command bit and inverter will respond with bit Operating When master clears the Switch on bit inverter will dece...

Страница 45: ...t direction Press MAN AUTO to go to Manual mode Set the frequency desired in display window Use and to change setpoint Positive frequency setpoint means clockwise rotation negative means counter clock...

Страница 46: ...PI reg Set actual value sensor measures at 10V 300 kPa using parameter Actual Max in parameter group PI reg Set the regulator amplification using parameter Reg Kp in parameter group PI reg Set regula...

Страница 47: ...0 AIN1 P positive and terminal 21 AIN1 N negative that gives the desired night time low frequency setting Connect a time relay or other contact between DIN4 PI reg and a 24V source When DIN4 terminal...

Страница 48: ...NFO Drives AB 2021 201013 2 Operating and Installation Manual 48 3006469 2022 04...

Отзывы: