CABLE PREPARATION
30
semi-conductive screen
1
Check distance of
200
mm.
2
Remove the semi-conductive screen to a point
30
mm from the outer sheath.
For extruded easy strip semi-conductive screen:
Cut squarely taking care not to cut the core insulation.
For bonded extruded semi-conductive screen:
Use an appropriate pencilling tool. Make a clean transition between core insulation and semi-conductive screen.
200
core insulation
conductor
protective
adhesive tape
2
Slightly bevel the edge of the core insulation (max 2 mm).
3
Thoroughly clean core insulation.
Always wipe towards the screen wires.
4
As a protection, wrap a few turns of adhesive tape around the conductor end.
bevel
REMOVAL OF THE CORE INSULATION
core insulation
conductor
contact
conductor
1
A. Remove the core insulation from the conductor
for a distance
« C »
mm
(
C
= depth of contact bore +
10
mm).
1
B. Remove the core insulation from the conductor
for a distance
« C »
mm
(
C
= depth of contact bore +
10
mm).
A. Compression type contacts (Type TBC-X)
B. Mechanical type contacts (Type TMBC-X)
10
C
core insulation
conductor
contact
conductor
10
C
IS97180-ENG - K800PB/G
-CW45-
CA0 - Revision 2
Page 4 of 14