In case the tee connector has been already installed
(otherwise proceed to step no. 6).
cable
clamp
earthing
lead
copper wire
screen
clamping
screw
basic
insulating
plug
Separable tee connector
protective
cap
1
Remove the protective cap from the tee connector. Put the
protective cap aside in a clean and safe place for later re-use.
2
Remove the basic insulating plug. Use a wrench with 22 mm
socket. Put the insulating plug aside in a clean and safe place
for later re-use.
3
Type 1
: remove the clamping screw. Use a wrench with a
22 mm socket and an extension. Put the clamping screw
aside in a clean and safe place for later re-use.
Type 2
: remove the flange nut. Use a wrench with a 22 mm
socket and an extension. Put the flange nut aside in a clean
and safe place for later re-use.Check that M16 stud is still
mounted correctly.
Re-tighten to 30 Nm if required.
Proceed with step 10
on page 10.
4
Disconnect the earthing lead, copper wire screen and cable
clamps.
5
Disconnect the tee connector from the bushing.
The bushing should be free.
basic
insulating
plug
protective
cap
Type 1
Type 2
COUPLING CONNECTOR INSTALLATION ON TEE CONNECTOR
M16
flange nut
Page 8 of 14
IS97180-ENG - K800PB/G
-CW45-
CA0 - Revision 2
For