* USE ONLY THE SILICONE LUBRICANT SUPPLIED
1
Lubricate* the indicated area: core insulation, semi-conductive screen, water sealing mastic and inner surface of the
reducer.
2
Slide the reducer down the cable until flush with the tape marker.
3
Remove the protective adhesive tape from the conductor.
INSTALLATION OF THE CABLE REDUCER
For conductor sizes 16 up to 150 mm²
core insulation
cable reducer
cable reducer
remove
protective
adhesive tape
lubricate
tape marker
1
Slide the installation rod on to the conductor until it butts against the core insulation.
2
Thoroughly clean installation rod and core insulation.
Always wipe towards the screen wires.
3
Lubricate* the indicated area: installation rod, core insulation, semi-conductive screen, water sealing mastic and
inner surface of the reducer.
4
Slide the reducer on to the installation rod.
5
Slide the reducer down the cable until flush with the tape marker. Take care to slide the reducer without hesitation
and in one smooth move.
6
Remove installation rod and protective adhesive tape from the conductor.
core
insulation
installation
rod
installation
rod
core insulation
lubricate
cable reducer
lubricate
tape marker
For conductor sizes 185 mm² up to 300 mm²
cable reducer
remove
protective
adhesive tape
Page 5 of 14
IS97180-ENG - K800PB/G
-CW45-
CA0 - Revision 2
For
information
only