- 27 -
(4) Analog span adjustment (Maintenance mode 2)
①
Set the Mode switch at 2 to select maintenance
mode 2.
②
Press down the reset key until the Power lamp
goes off.
③
The Power lamp lights up again and the auto
span adjustment value is reset.
④
Set the Mode switch at 1 to select maintenance
mode 1.
⑤
Confirm that the zero point is at zero and apply
calibration gas to the gas detector for a minute.
⑥
Set the Mode switch at 2 to select maintenance
mode 2.
POWER
ALARM
2
1
RESET
BZSTOP
BACK UP
Peak hold
value
On
POWER
ALARM
2
1
RESET
BZSTOP
BACKUP
Always perform analog zero adjustment before doing analog span adjustment. Otherwise the span cannot be
adjusted properly when the analog span adjustment is performed.
CAUTION