- 22 -
⑦
Press the test button and simultaneously turn
the test volume until the reading matches the
peak hold value.
⑧
Then adjust the span adjustment volume
(SPAN) and adjust the indication value to the
calibration gas concentration.
⑨
Release the test button and confirm that the
indicated value indicates 1.0.
⑩
Press down the test button and adjust the
indication value to full scale.
⑪
Set the Mode switch at zero to return to normal
mode.
⑫
Apply the calibration gas and check to see if the
gas concentration is indicated correctly.
Match the peak
hold value.
POWER
ALARM
2
1
RESET
BZ STOP
POWER
ALARM
2
1
RESET
BZ STOP
Check to see if
the reading
returns to 1.0.
Return to the
Full scale.
POWER
ALARM
2
1
RESET
BZ STOP
POWER
ALARM
2
1
RESET
BZ STOP
Make sure that there is
no gas around the gas
detector and check to
see if the indicator
reads 1.0.
Note that a gas leak alarm and external output will be generated when calibration gas is applied in normal
mode.
CAUTION
BACK UP
POWER
ALARM
2
1
RESET
BZSTO
Scale for
calibration gas
concentration
BACK UP
BACK UP
BACK UP
POWER
ALARM
2
1
RESET
BZ STOP
Check the
calibration
concentration
reading.
BACK UP
BACK UP