- 20 -
(1) Zero and span adjustment without linearizer specifications
1) Analog zero adjustment (Maintenance mode 2)
①
Set the Mode switch at 2 to select maintenance
mode 2.
②
Press down the BZ STOP key until the Power
lamp goes off.
③
The Power lamp lights up again and the auto
zero adjustment value is reset.
④
Make sure that there is no gas around the gas
detector then turn the zero adjustment
volume (ZERO) to set the indicated value to 1.0.
⑤
Set the Mode switch at zero to return to normal
mode.
POWER
ALARM
2
1
RESET
BZ STOP
BACKUP
Off
Use the analog zero and span adjustment method to adjust non-linearizer models.
MEMO
POWER
ALARM
2
1
RESET
BZ STOP
BACK UP
Peak hold value
POWER
ALARM
2
1
RESET
BZ STOP
Adjust the
indicator to read
1.0.
POWER
ALARM
2
1
RESET
BZ STOP
On
BACK UP
BACKUP
POWER
ALARM
2
1
RESET
BZ STOP
Check to see if
the indicator
reads 1.0.
BACK UP