Safety Requirements

This section details the requirements for safe installation and operation of the UX system. Be sure to review this information before placing the system
into operation.

1. 

 - The product is for use in a 

 only.

Restricted Access

Restricted Access Location

2. 

 - The equipment has provision for a permanently connected protective earthing conductor. Attach a 14 AWG copper

Grounding the UX2000 equipment

wire and a 1-hole UL approved lug to the grounding connection. Use Panduit PN14-6R or equivalent.

3. Rack Mount Instructions
(a) 

 - If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be

Elevated Operating Ambient

greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum
ambient temperature specified by the manufacturer.
(b) 

 - Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is

Reduced Air Flow

not compromised.
(c) 

 - Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical

Mechanical Loading

loading.
(d) 

 - Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the

Circuit Overloading

circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when
addressing this concern.
(e) 

 - Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections

Reliable Earthing

other than direct connections to the branch circuit (e.g., use of power strips).

4. 

 - Notes for Replaceable batteries and Telephone line cord.

CAUTION

(a) 

 - CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries According to the Instructions.

Replaceable Batteries

(b) 

 - CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger (e.g., 24 AWG) UL Listed or CSA Certified Telecommunication

Telephone Line Cord

Line Cord.

5.Nordic Country Notice
(a) 

: "Laite on liitettävä suojamaadoitus¬koskettimilla varustettuun pistorasiaan"

For Finland

    

: "Apparatet må tilkoples jordet stikkontakt"

For Norway

    

: "Apparaten skall anslutas till jordat uttag"

For Sweden

(b) The equipment must be installed only in a 

.

Restricted Access Location

(c) The systems installed in Sweden, Finland and Norway must have supplementary grounding terminal at the chassis frame for the permanent
connection of grounding conductor described in 

.

System Grounding Requirements

For additional information, please review the following sections:

Power Connection Requirements
Restricted Access Location Requirements
System Grounding Requirements

Power Connection Requirements

This section describes the requirements for wiring of power connections to the UX system.

Power Connections and Wiring

United States and Canada
Europe

For more information about grounding requirements for the UX system, see 

. For more information the power supply

System Grounding Requirements

Содержание SBC 2000

Страница 1: ...NET Confidential Copyright 2011 Network Equipment Technologies Inc All Rights Reserved NET UX SYSTEMS Unified Communications Exchange Customer Documentation DRAFT September 2011...

Страница 2: ...Branch Appliance ASM 14 1 5 2 2 Digital Signal Processing DSP Modules 15 1 5 3 Safety Precautions 15 1 5 3 1 Electrostatic Discharge ESD Precautions 16 1 5 4 Safety Requirements 17 1 5 4 1 Power Conn...

Страница 3: ...Solution Module ASM Digital Signal Processing DSP Modules Safety Precautions Electrostatic Discharge ESD Precautions Safety Requirements Power Connection Requirements Restricted Access Location Requir...

Страница 4: ...cipating in a peer relationship The normal state of this LED is off 4 Ready Status LED This status LED indicates if the UX system is ready to process calls The normal state of this LED is on and green...

Страница 5: ...s LED 4 Alarm Alarm Status LED 5 Peer Node Peer Node Status LED 6 Ready Ready Status LED 7 Admin System Administration Ethernet Port 8 Port 1 Primary Application Ethernet Port 1 9 Ports 2 4 Ethernet P...

Страница 6: ...er Interface Description Monitor Tab Tasks Tab Settings Tab Logs Tab System Tab UX System Hardware Reference This section contains physical and electrical specifications for the chassis and expansion...

Страница 7: ...E1 PSTN Interface Cards Compliance and Regulatory Information This section provides various compliance and regulatory information related to the safety and operation of the UX product Declaration of...

Страница 8: ...ty Information Product Emission Class The UX system is a Class A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate mea...

Страница 9: ...otection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can create radio frequency energy and if not installed and used in ac...

Страница 10: ...limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio freque...

Страница 11: ...ACTA adapted ANSI TIA 968 B standard or it must be connected through protective circuitry that is approved by N E T and registered in accordance with the ACTA adapted ANSI TIA 968 B standard Newly Es...

Страница 12: ...ith you distributor as to the surge protector requirements for your equipment Industry Canada Equipment Attachment Limitations The following notices are required by Industry Canada Terminal Attachment...

Страница 13: ...telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of RENs should not exceed five 5 0 To be ce...

Страница 14: ...s using N E T products with programmed dialer features stay on the line and briefly explain to the dispatcher the reason for the call before hanging up Perform these activities in off peak hours such...

Страница 15: ...cause hardware components to overheat and fail Unauthorized removal of the top panel will void your product warranty and service agreement Application Solution Module ASM Digital Signal Processing DS...

Страница 16: ...ectrical situations in the following topics AC Power Electrical AC Power The following information provides safety precautions to follow when using this equipment Always disconnect the power source to...

Страница 17: ...unding strap connected to a proper ground when handling modules Keep boards in their antistatic protection bags until you are ready to install them Do not touch pins leads or solder connections on the...

Страница 18: ...e consideration of equipment nameplate ratings should be used when addressing this concern e Reliable earthing of rack mounted equipment should be maintained Particular attention should be given to su...

Страница 19: ...ation PVC Conductor Stranded Europe Requirements Minimum Wire Size 1 63 mm Minimum Voltage Rating 300 V Insulation PVC Conductor Stranded Use only the AC power cord s supplied with the UX system After...

Страница 20: ...ating 300 V Conductor Stranded Europe Grounding Connections Requirements Minimum Wire Size 1 63 mm Minimum Voltage Rating 300 V Conductor Stranded Connecting the UX Chassis to Earth Ground When instal...

Страница 21: ...urce This section describes the dimensional environmental power and network specifications and requirements for the UX2000 System Dimensions and Weight Environmental Ranges Operation and Storage Power...

Страница 22: ...Replace the UX1000 power supply units with NET provided units only Specifications Specifications The UX system comes equipped with a single power supply which complies with the following specification...

Страница 23: ...UX power supplies are tested and certified to meet UL cUL IEC 60950 1 safety requirements For more information about the UX power supply units see UX2000 Power Supplies Networking Interfaces The UX200...

Страница 24: ...PSTN Interface Cards Inserting and Removing Interface Cards This section describes the steps for inserting and removing from the rear of the UX chassis Interface Cards Review and follow the UX before...

Страница 25: ...o Insert an Interface Card Carefully insert the card so that the left and right edges slide into the mounting slots Grip the outside of the attachment levers and push toward the inside of the card unt...

Страница 26: ...rd has board mounted protection circuits for electrical isolation and protection against power crossing lightning surges and hazardous voltages Card Port Versions Port Status LEDs Hot Swap Status LED...

Страница 27: ...icates the port has a Loss Of Framing LOF error A cable is connected but UX can not detect a correct T1 or E1 frame Amber Yellow Indicates there is a problem with the far end connection This status is...

Страница 28: ...ation Warnings Preparing for Installation Installing the UX Chassis in a 4 Post Equipment Rack Installing the UX Chassis in a 2 Post Equipment Rack Installing Interface Cards Installing Ground Wire Po...

Страница 29: ...he UX Chassis in a 4 Post Equipment Rack The UX2000 chassis can be installed in a standard 19 inch 4 post equipment racks Mounting hardware is provided for racks with 24 inch and 30 inch depths Before...

Страница 30: ...ng ears securely to the front corners of the UX chassis Attach the 2 pan handle plates securely to the rear corners of the UX chassis Working with a partner lift the UX chassis and slide it into the e...

Страница 31: ...000 chassis using only the rack ears attached to the front corners on a 2 post equipment rack Mounting the chassis using only the front mount rack ears will not provide adequate mechanical support and...

Страница 32: ...face Cards You must power down the UX system before installing or removing Interface Cards Hot swapping of Interface Cards is not supported in UX 1 2 To Insert an Interface Card Carefully insert the c...

Страница 33: ...on of the UX chassis connect the grounding wire and power cables To Install the Grounding Wire and Power Cables Connect a grounding wire to the grounding bolt on the left side of the rear panel in acc...

Страница 34: ...ment Bracket Place the cable management bracket on top of the pan handle plates If you have installed the UX chassis in a 2 post configuration you must install the pan handle plates on the rear corner...

Страница 35: ...assis can be mounted in a standard seven 7 foot rack These space requirements must be met to comply with Telcordia and Euro ISDN ETSI standards When installing the chassis allow space around the chass...

Страница 36: ...lding ground network For ground wire specifics see the tables below for the United States Canada and Europe Only qualified service personnel should perform the electrical procedures for grounding wire...

Страница 37: ...he chassis More than one chassis can be mounted in a standard seven 7 foot rack These space requirements must be met to comply with Telcordia and Euro ISDN ETSI standards When installing the chassis a...

Страница 38: ...he building ground network For ground wire specifics see the tables below for the United States Canada and Europe Only qualified service personnel should perform the electrical procedures for groundin...

Отзывы: