Location of the ESD Plug on the UX2000 Chassis Rear Panel
Safety Requirements
This section details the requirements for safe installation and operation of the UX system. Be sure to review this information before placing the system
into operation.
1.
- The product is for use in a
only.
Restricted Access
2.
- The equipment has provision for a permanently connected protective earthing conductor. Attach a 14 AWG copper
Grounding the UX2000 equipment
wire and a 1-hole UL approved lug to the grounding connection. Use Panduit PN14-6R or equivalent.
3. Rack Mount Instructions
(a)
- If installed in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be
Elevated Operating Ambient
greater than room ambient. Therefore, consideration should be given to installing the equipment in an environment compatible with the maximum
ambient temperature specified by the manufacturer.
(b)
- Installation of the equipment in a rack should be such that the amount of air flow required for safe operation of the equipment is
Reduced Air Flow
not compromised.
(c)
- Mounting of the equipment in the rack should be such that a hazardous condition is not achieved due to uneven mechanical
Mechanical Loading
loading.
(d)
- Consideration should be given to the connection of the equipment to the supply circuit and the effect that overloading of the
Circuit Overloading
circuits might have on overcurrent protection and supply wiring. Appropriate consideration of equipment nameplate ratings should be used when
addressing this concern.
(e)
- Reliable earthing of rack-mounted equipment should be maintained. Particular attention should be given to supply connections
Reliable Earthing
other than direct connections to the branch circuit (e.g., use of power strips).
4.
- Notes for Replaceable batteries and Telephone line cord.
CAUTION
(a)
- CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries According to the Instructions.
Replaceable Batteries
(b)
- CAUTION: To reduce the risk of fire, use only No. 26 AWG or larger (e.g., 24 AWG) UL Listed or CSA Certified Telecommunication
Telephone Line Cord
Line Cord.
5.Nordic Country Notice
(a)
: "Laite on liitettävä suojamaadoitus¬koskettimilla varustettuun pistorasiaan"
For Finland
: "Apparatet må tilkoples jordet stikkontakt"
For Norway
: "Apparaten skall anslutas till jordat uttag"
For Sweden
(b) The equipment must be installed only in a
.
(c) The systems installed in Sweden, Finland and Norway must have supplementary grounding terminal at the chassis frame for the permanent
connection of grounding conductor described in
.
For additional information, please review the following sections:
Power Connection Requirements
Restricted Access Location Requirements
System Grounding Requirements
Power Connection Requirements
This section describes the requirements for wiring of power connections to the UX system.
United States and Canada
Europe
For more information about grounding requirements for the UX system, see
. For more information the power supply