United States and Canada Grounding Connections
Europe Grounding Connections
Connecting the UX Chassis to Earth Ground
To Ground the UX2000 System
To Ground the UX1000 System
Grounding Requirements
UX Series equipment must be grounded to the building ground network. For ground wire specifics, see the tables below for the United States, Canada
and Europe.
Only qualified service personnel should perform the electrical procedures for grounding wire installation.
United States and Canada Grounding Connections
Requirements
Minimum Wire Size
14 AWG
Minimum Voltage Rating
300 V
Conductor
Stranded
Europe Grounding Connections
Requirements
Minimum Wire Size
1.63 mm
Minimum Voltage Rating
300 V
Conductor
Stranded
Connecting the UX Chassis to Earth Ground
When installing the chassis, connect the earth ground wires from the UX chassis to the facility ground bus.
You must provide connections between the earth ground connection points on the chassis and the facility ground bus. To avoid a
potential electrical hazard, be sure to confirm that the system power supplies are physically disconnected from the power feed before
installing the wires.
Use the grometed holes on the right and left flanges of the rack, as the attachment points for the safety ground wiring described in the following
procedure.
Ground Connections on Left Rear Panel of the UX2000