7.2.1 Min Time / MaxTime / Data Variation
FPort
:
0x07
Description
Cmd
ID
Device
Type
NetvoxPayLoadData
Config
ReportReq
0x01
0xD2
MinTime
(2bytes)
Unit:s)
MaxTime
(2bytes)
Unit:s
Battery
Change
(1byte)
Unit:0.1v
Temperature
Change
(2bytes)
Unit:0.01°C
Humidity
Change
(1byte)
Unit:0.5 %
Illuminance
Change
(1byte)
Unit
:
1Lux
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes)
Unit:s
MaxTime
(2bytes)
Unit:s
Battery
Change
(1byte)
Unit:0.1v
Temperature
Change
(2bytes)
Unit:0.01°C
Humidity
Change
(1byte)
Unit:0.5 %
Illuminance
Change
(1byte)
Unit
:
1Lux
1.
Configure device parameters MinTime = 1min, MaxTime = 1min, BatteryChange = 0.1v,
TemperatureChange = 10°C, HumidityChange = 20%,
Illuminancechange = 100lux
Downlink: 01D2003C003C0103E82864
1
st
byte (01): CMD ID
2
nd
byte (D2): DeviceType 0XD2
-
R315 Series
3
rd
4
th
byte (003C): Min Time, 003C(Hex)=60(Dec), 60s
5
th
6
th
byte (003C): Max Time, 003C(Hex)=60(Dec), 60s
7
th
byte (01): Battery Change, 0.1v
8
th
9
th
byte (03E8): Temperature Change, 03E8(Hex) = 1000(Dec), 1000*0.01°C=10°C
10
th
byte (28): Humidity Change, 28(Hex)=40(Dec), 40*0.5%=20%
11
th
byte (64): Illuminance Change, 64(Hex)=100(Dec), 100*1 lux=100 lux
Response:
81D2000000000000000000
(
Configuration success
)
81D2010000000000000000
(
Configuration failure
)