23
7.2.10 ConfigDryContactINTriggerTime
FPort
:
0x0F
Description
CmdID
PayLoad(Fix byte,2byte)
SetDryContactIN
TriggerTimeReq
0x01
MinTriggeTime (2bytes)
(Unit:1ms,Default 50ms)
SetDryContactIN
TriggerTimeRsp
0x81
Status
(0x00_Success 0x01_Failure)
Reserved
(1Byte,Fixed 0x00)
GetDryContactIN
TriggerTimeReq
0x02
Reserved
(2Byte,Fixed 0x00)
GetDryContactIN
TriggerTimeRsp
0x82
MinTriggeTime (2bytes)
(Unit:1ms,Default 50ms)
Set trigger time =100ms
Downlink:010064
Response:
810000
(
Configuration success
)
820100
(
Configuration failure
)
Note:
1.
The issuing port is 0x0F
2. Default is 50ms
7.3 Example for MinTime/MaxTime logic
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e.
Battery Voltage Change=0.1V
Note:
MaxTime=MinTime.
Data will only be report according to
MaxTime (MinTime)
duration regardless
Ba
ttery Voltage Change value.
0H
1H
2H
Wake up and collects data
REPORTS 2.8V
Wakes up and collects data
REPORTS 2.8V
Wakes up and collects data
REPORTS 2.8V
Max Time
Max Time
Min Time
Min Time
(Sleeping)
(Sleeping)