background image

MAN-0093 Rev 0 Oxygen Sensor 
June 2008 
Net Safety Monitoring Inc. 

 

 

 

SECTION 1:  Plan 

1.1 Locate Sensor 

Prior to the installation process, a location plan for placing the sensor should be developed. Although there are 
no absolute rules determining the quantity of detectors or location of a sensor, the following points should be 
considered when planning the installation. 
 

 

Carefully locate the sensor in an area where gases may potentially accumulate. (Remember, light gases 
tend to rise and heavy gases tend to accumulate in low areas). 

 

Use redundant systems to enhance protection and reliability. 

 

Consider the air movement patterns within the facility. 

 

Consider the construction of the facility such as trenches where heavy gases or peaks where light gases, 
may accumulate. 

 

Seek advice from experts knowledgeable about the primary gas to be detected. 

 

Use common sense and refer to the regulatory publications that discuss guidelines for your industry. 

 

1.2 Sensor Non-Separated 

The sensor is attached directly to a transmitter and located in the appropriate location for detecting the gas in 
question. 

 

                                                                                                     Figure 3:  Locating Sensor

 

1.3 Sensor Separated 

Locate the sensor separate from a transmitter using a 
‘junction box / separation kit’. The transmitter is located 
near eye-level for easy access and the sensor is located 
where the gas is likely to accumulate. A calibration cup is 
clipped onto the bottom of the sensor housing and the 
calibration tubing is attached to the calibration cup and 
runs to a convenient place for applying calibration gas(air) 
eliminating the need to access the sensor directly.  
 
To compensate for distance when remotely calibrating, in 
separation orientation, decrease the tubing diameter or 
increase the calibration gas flow rate between the gas 
canister and sensor. On initial install, always confirm 
tubing run is not affecting calibration. Calibrate the sensor 
using tubing run and then confirm readings directly at 
sensor by applying calibration gas (air) and comparing the 
output results. They should be accurate to the calibration 
gas concentration used.  
 

 
 

Sensor

Conduit to

Controller

Apply Calibration Gas

Controller

Calibration Cup

About
eye
level

Содержание ST340X-25-ASSY

Страница 1: ...Part Number MAN 0093 Rev 0 June 2008 MILLENNIUM II Gas Sensor Oxygen O2 Sensor User Manual Model ST340X 25 ASSY...

Страница 2: ...roughly tested inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance ins...

Страница 3: ...wer Up 10 3 3 Sensor Communication 10 SECTION 4 Output 11 4 1 Alarm and Fault Outputs 11 4 1 1 Other Available Outputs 11 4 1 2 Modbus registers 11 SECTION 5 Maintaining 12 5 1 Millennium II Basic Tra...

Страница 4: ...sor June 2008 Net Safety Monitoring Inc 4 5 6 How to Return Equipment 19 Appendix 20 Appendix A Electrostatic Sensitive Device ESD 20 Appendix B Resistance Table 21 Appendix C Millennium II Oxygen O2...

Страница 5: ...or hazardous locations and a replaceable sensor module This sensor is designed to only operate with the Millennium II series Transmitters If the sensor is connected to any other model transmitters it...

Страница 6: ...Basic sensor I J in mm in mm Transmitter sensor AL 3 0 76 9 0 229 Transmitter sensor SS 2 8 71 8 9 226 Figure 2 below shows the dimensions of the Millennium II transmitter with sensor and the Millenni...

Страница 7: ...MAN 0093 Rev 0 Oxygen Sensor June 2008 Net Safety Monitoring Inc 7 Figure 2 Sensor with Millennium II series transmitters dimensional drawing...

Страница 8: ...s attached directly to a transmitter and located in the appropriate location for detecting the gas in question Figure 3 Locating Sensor 1 3 Sensor Separated Locate the sensor separate from a transmitt...

Страница 9: ...l equipment in a hazardous area and is the responsibility of the installer If in doubt consult a qualified official before wiring the system Guidelines When separating the sensor from the transmitter...

Страница 10: ...Junction Box Manual MAN 0081 for terminal designations SECTION 3 Operation 3 1 Configuration Settings All configuration settings are accessed through the Millennium II series transmitter This is done...

Страница 11: ...tter manual for more information 4 1 2 Modbus registers Table 4 below shows the user accessible Modbus registers and meaning Table 4 Modbus registers and meaning Reg Meaning Readable Writeable 40001 C...

Страница 12: ...low and Below Above The default Alarm Mode is Below Below Above Above means the alarm will be activated when oxygen level is above Alarm Point 1 or above Alarm point 2 Below Below means the alarm will...

Страница 13: ...arm Mode Below Above Alarm Point 1 and Alarm Point 2 are distinct as seen in Table 9 Table 7 Alarm Points for Alarm Mode Above Above Alarm Mode Above Above Alarm Point 1 2 Position 1 position 3 Positi...

Страница 14: ...n or magnet after which status LED goes solid red release push button or remove magnet 6 When the current output is 3 mA indicated by analog models and the Status LED is once again solid green second...

Страница 15: ...menu button 2 Reed switch 2 or menu button 1 Reed switch 1 to navigate Alarm Mode Setting Select this option with menu button 3 Reed switch 3 3 The display will show Only for Oxygen Sensor and then sh...

Страница 16: ...n press select menu button 1 or Reed switch 1 to select yes 2 When Calibrate Sensor is displayed select the enter key menu button 3 or Reed switch 3 3 When Calibrate Sensor 1 is highlighted press the...

Страница 17: ...sensor housing by turning in a counter clockwise rotation to expose sensor module 4 Using the Teflon pull tab pull sensor straight down out of the sensor housing until sensor is completely removed fro...

Страница 18: ...libration If the problem persists please contact Net safety s service department first by phone to try and resolve the issue If the issue cannot be resolved please follow the procedure below on how to...

Страница 19: ...an determine and correct the problem 3 A company name contact name and telephone number 4 A purchase order from your company authorizing repairs or request for quote 5 Ship all equipment prepaid to Ne...

Страница 20: ...mingly normal for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch el...

Страница 21: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Страница 22: ...Oxygen O2 Performance Response Time T95 15 sec Zero Drift 5 per year Environmental Temperature Operational 40 C to 50 C RH 0 99 RH non condensing Metallurgy Aluminum or 316 SS Nema Rating NEMA 4X Sep...

Страница 23: ...Calgary AB Canada T1Y 7J7 1 866 FIREGAS 347 3427 ph 403 219 0688 fx 403 219 0694 http www net safety com info net safety com PRODUCT SERVICES CONTACT INFORMATION Telephone 8am 5pm MDT 403 769 6074 403...

Отзывы: