background image

MAN-0093 Rev 0 Oxygen Sensor 
June 2008 
Net Safety Monitoring Inc. 

 

 

10 

 

2.3.2 Sensor Wiring 

 
Warning

 

Do not open the transmitter in a classified area(Do not open when an explosive atmosphere 

may be present).  Ensure the power to the transmitter is switched off before connecting sensor wires. 

 
Warning

 

 

Avoid touching electronic components, as they are susceptible to electrostatic discharge 

(ESD). Refer to Appendix A, “Electrostatic Sensitive Device (ESD)”. 

 

Connect the colored sensor wires to the sensor terminals in the applicable transmitter. Refer to the Table 3 for 
the sensor terminal definitions. 

 
       

Table 3: Sensor Terminal Definitions of Millennium II Transmitters 

Sensor

 

Terminals

 

Sensor

 

Wire

 

White

 

Red

 

Blue

 

Black

 

Green

 

Marked

 

+VDC

 

Sig

 

A

 

Sig

 

B

 

COM

 

Shld

 

Function

 

10.5

 ‐ 

32VDC

 

A

 

B

 

Common/Supply

 

Ground

 

Earth

 

Ground

 

 

 

NOTE: 

When separating sensor from transmitter using Net Safety separation kit, refer to Multi-purpose 

Junction Box Manual (MAN-0081) for terminal designations. 

 

SECTION 3:  Operation 

3.1 Configuration Settings 

All configuration settings are accessed through the Millennium II series transmitter.  This is done by setting dip 
switches on the Millennium II Basic and by selecting menu options in the Millennium Transmitter. See relevant 
transmitter manual. 
 

3.2 Sensor Power Up 

 

When power is applied to the sensor, a 60 second power up routine will begin, where the sensor is being 
automatically tested to ensure proper functionality. Refer to applicable Millennium II transmitter manual for 
status indications during this period. 

 

3.3 Sensor Communication 

The ST340 sensor uses a proprietary protocol to communicate to the Millennium II transmitter series. The 
sensor should never be connected to any device other than the Millennium II series transmitters. Selected dip 
switches and menu options are communicated to the sensor by the transmitter. These configurations are stored in 
the sensor’s memory. If the configuration settings are not done correctly, the sensor will not communicate 
properly with the transmitter. 
 

Содержание ST340X-25-ASSY

Страница 1: ...Part Number MAN 0093 Rev 0 June 2008 MILLENNIUM II Gas Sensor Oxygen O2 Sensor User Manual Model ST340X 25 ASSY...

Страница 2: ...roughly tested inspected and calibrated prior to shipment Failures can occur which are beyond the control of the manufacturer Failures can be minimized by adhering to the operating and maintenance ins...

Страница 3: ...wer Up 10 3 3 Sensor Communication 10 SECTION 4 Output 11 4 1 Alarm and Fault Outputs 11 4 1 1 Other Available Outputs 11 4 1 2 Modbus registers 11 SECTION 5 Maintaining 12 5 1 Millennium II Basic Tra...

Страница 4: ...sor June 2008 Net Safety Monitoring Inc 4 5 6 How to Return Equipment 19 Appendix 20 Appendix A Electrostatic Sensitive Device ESD 20 Appendix B Resistance Table 21 Appendix C Millennium II Oxygen O2...

Страница 5: ...or hazardous locations and a replaceable sensor module This sensor is designed to only operate with the Millennium II series Transmitters If the sensor is connected to any other model transmitters it...

Страница 6: ...Basic sensor I J in mm in mm Transmitter sensor AL 3 0 76 9 0 229 Transmitter sensor SS 2 8 71 8 9 226 Figure 2 below shows the dimensions of the Millennium II transmitter with sensor and the Millenni...

Страница 7: ...MAN 0093 Rev 0 Oxygen Sensor June 2008 Net Safety Monitoring Inc 7 Figure 2 Sensor with Millennium II series transmitters dimensional drawing...

Страница 8: ...s attached directly to a transmitter and located in the appropriate location for detecting the gas in question Figure 3 Locating Sensor 1 3 Sensor Separated Locate the sensor separate from a transmitt...

Страница 9: ...l equipment in a hazardous area and is the responsibility of the installer If in doubt consult a qualified official before wiring the system Guidelines When separating the sensor from the transmitter...

Страница 10: ...Junction Box Manual MAN 0081 for terminal designations SECTION 3 Operation 3 1 Configuration Settings All configuration settings are accessed through the Millennium II series transmitter This is done...

Страница 11: ...tter manual for more information 4 1 2 Modbus registers Table 4 below shows the user accessible Modbus registers and meaning Table 4 Modbus registers and meaning Reg Meaning Readable Writeable 40001 C...

Страница 12: ...low and Below Above The default Alarm Mode is Below Below Above Above means the alarm will be activated when oxygen level is above Alarm Point 1 or above Alarm point 2 Below Below means the alarm will...

Страница 13: ...arm Mode Below Above Alarm Point 1 and Alarm Point 2 are distinct as seen in Table 9 Table 7 Alarm Points for Alarm Mode Above Above Alarm Mode Above Above Alarm Point 1 2 Position 1 position 3 Positi...

Страница 14: ...n or magnet after which status LED goes solid red release push button or remove magnet 6 When the current output is 3 mA indicated by analog models and the Status LED is once again solid green second...

Страница 15: ...menu button 2 Reed switch 2 or menu button 1 Reed switch 1 to navigate Alarm Mode Setting Select this option with menu button 3 Reed switch 3 3 The display will show Only for Oxygen Sensor and then sh...

Страница 16: ...n press select menu button 1 or Reed switch 1 to select yes 2 When Calibrate Sensor is displayed select the enter key menu button 3 or Reed switch 3 3 When Calibrate Sensor 1 is highlighted press the...

Страница 17: ...sensor housing by turning in a counter clockwise rotation to expose sensor module 4 Using the Teflon pull tab pull sensor straight down out of the sensor housing until sensor is completely removed fro...

Страница 18: ...libration If the problem persists please contact Net safety s service department first by phone to try and resolve the issue If the issue cannot be resolved please follow the procedure below on how to...

Страница 19: ...an determine and correct the problem 3 A company name contact name and telephone number 4 A purchase order from your company authorizing repairs or request for quote 5 Ship all equipment prepaid to Ne...

Страница 20: ...mingly normal for an indefinite period of time followed by a sudden failure To eliminate potential ESD damage review the following guidelines Handle boards by metal shields taking care not to touch el...

Страница 21: ...1 09 0 63 1250 12 70 7 99 5 03 3 16 1 99 1 25 0 79 1500 15 20 9 58 6 02 3 79 2 38 1 50 0 94 1750 17 80 11 20 7 03 4 42 2 78 1 75 1 10 2000 20 30 12 80 8 03 5 05 3 18 2 00 1 26 2250 22 80 14 40 9 03 5...

Страница 22: ...Oxygen O2 Performance Response Time T95 15 sec Zero Drift 5 per year Environmental Temperature Operational 40 C to 50 C RH 0 99 RH non condensing Metallurgy Aluminum or 316 SS Nema Rating NEMA 4X Sep...

Страница 23: ...Calgary AB Canada T1Y 7J7 1 866 FIREGAS 347 3427 ph 403 219 0688 fx 403 219 0694 http www net safety com info net safety com PRODUCT SERVICES CONTACT INFORMATION Telephone 8am 5pm MDT 403 769 6074 403...

Отзывы: