Compact Make-up Air Unit
Specification and Installation Instructions
www.neptronic.com
Page | 6
Wall Mounting
•
Prior to installation, ensure that the strength of the chosen wall and supports conform to the requirements of local codes
and regulations. The use of metal strut channels is recommended when wall mounting the unit (by others).
•
Mount the unit at a minimum height of 6.5ft (2m) above the floor level.
•
Mount the CMU using at least 2 screws of minimum #10 (M5) size (by others) using the keyholes located in the back of the
unit and ensure that the installation is secure.
Use 2 screws
(by others)
Ceiling Installation
•
The CMU can be hung by the ceiling using an appropriate support platform (by others). Consult local codes and
regulations for minimum structural requirements for such platforms.
•
The CMU must be attached to the platform by use of 4 self-drilling screws of #10 (M5) size fixed at the designated
locations indicated by the dimples on the bottom of the unit, as per the image below.
•
The screws must not be inserted into the CMU at a depth of more than ¾
” (20mm).
•
Ensure not to install the bottom of
the unit’s front access panel directly onto the platform, as this will prevent it from
opening.
7.75"
(197mm)
1.75"
(45mm)
1.75"
(45mm)
1.75"
(45mm)
1.75"
(45mm)
Bottom View: Location of Mounting Holes