![Neptronic CMU Series Скачать руководство пользователя страница 17](http://html.mh-extra.com/html/neptronic/cmu-series/cmu-series_specification-and-installation-instructions_1667972017.webp)
Compact Make-up Air Unit
Specification and Installation Instructions
www.neptronic.com
Page | 17
Menu 757
– Configuration
End
(exit menu)
OfSt
(off set)
Optn
(options)
PID
(PI D cont rol)
Config
StPt
(set point)
= scroll menu items
Exit menu and ret urn
to normal operation
TEMP SETPNT SOURCE
OnBo
(on board)
TSTA
(thermostat)
NET
(network)
TEMP SETPNT LOCK
ON
OFF
TEMP MIN SETPNT
15°C/59°F
(
0° C-35°C/32°F-212° F
)
TEMP MAX SETPNT
25°C/77°F
(
0° C-35°C/32°F-212° F
)
SAT CONTROL BAND
3°C/37°F
(2-10°C/36-50°F)
OCCUP AIRFLOW STPNT PERCENT
100%
(0-100%)
UNOCC AIRFLOW STPNT PERCENT
100%
(0-100%)
DRYMODE SETPNT
50%
(10-90%)
DRYMODE DEADBND
5%
(1-10%)
OCCUP PRESSUR SETPNT PASCAL
150Pa
(0-1250Pa)
UNOCCUP PRESSUR SETPNT PASCAL
150Pa
(0-1250Pa)
CO2 SETPNT PPM
800PPM
(0-1000PPM)
CO2 dEADBND ppm
200PPM
(0-200PPM)
TEMP AUTO PID
ON
OFF
TEMP INTEGRA TIME
10 sec
(0-255 sec)
TEMP PROP BAND
TEMP DERIVAT TIME
0 sec
(0-255 sec)
2.0°C/36°F
(0.5°C-20°C/33°F-68°F)
ST PRSS PROP BAND
10Pa
(0-250Pa)
ST PRSS INTEGRA TIME
10 sec
(0-255 sec)
ST PRSS DERIVAT TIME
0 sec
(0-255 sec)
SAT OFFSET
Actual °C/°F
(±5°C/ 9°F)
OAT OFFSET
SARH OFFSET
OARH OFFSET
ENABLE OCCUP INPUTS
No
OCCUP INPUTS INACTV MODE
Unoc
(unoccupied)
TOP LINE VALUE
None
DISP TEMP VALUE
DFLT
(default )
Yes
OFF
Time
CO2
(carbon dioxide)
SARH
(supply air relat ive humidity)
RARH
(room air relative humidity)
ALT
(alternate)
SAT
(supply air temperat ure)
TSTA
(Thermostat)
MSV. 19
BV.17
MSV. 18
BV.13
MSV. 2
BV.10
BV.37
AV.22
AV.23
AV.44
AV.13
AV.14
AV.24
AV.25
AV.26
AV.27
AV.28
AV.29
AV.39
AV.40
AV.38
AV.30
AV.32
AV.31
AV.33
AV.41
AV.42
AV.43
Returns to run mode
Go to
OfSt
Go to
SCHd
Go to
PID
Actual °C/°F
(±5°C/ 9°F)
Actual %RH
(±5 %RH)
Actual %RH
(±5 %RH)
SCHd
(schedule)
End
(exit menu)
SCHd
(schedule)
dAtE
(Date)
Schedul
HrS
(time)
Opt
(options)
Format
12h
24h
Hours
00
(00-23)
Minutes
00
(00-59)
Go to
dAtE
Year
Month
01
(01-12)
Day
01
(01-31)
Go to
Opt
2000
(2000-2136)
Enable Schedule
No
Yes
Schedul Default Value
Occ
(occupancy)
nOcc
(non occupancy)
Off
Schedul PRIO For Writing
16
(1-16)
Reset Schedule
No
Yes
Go to
SCHd
Day of Week
Fr
(Friday)
Sa
(Sat urday)
Su
(Sunday)
E1 00:00
E1 - E6
(event)
00 - 23 hours
00, 15, 30, 45 minutes
OFF, Occ
(occupancy)
, nOcc
(non occupancy)
, --
(null)
Go to
Optn
Exit menu and
go to
Optn
= scroll menu items
mo
(Monday)
tu
(Tuesday)
wE
(Wednesday)
th
(Thursday)
= select / set value
*** To save any changes, press on TDF ***
*** To return to the previous step without saving, press on TDF ***
= select / set value
= select / set value
Содержание CMU Series