Compact Make-up Air Unit
Specification and Installation Instructions
www.neptronic.com
Page | 5
Clearance
•
Leave a minimum clearance of
24’’ (610mm) or equivalent to the length of the front access panel/door (see dimension E
on page 3)
+ 1.5” (38mm) at the front of the unit, in order to provide sufficient space for accessing the electrical
compartment and air filter, to ensure proper servicing.
•
Other surfaces require zero clearance.
Minimum 24"
(610mm)
Insulation
•
Insulation may be added around the main surfaces of the CMU for energy conservation and noise reduction. The collars
and ductwork preceding and following the CMU may be insulated.
•
Insulation must be rated for temperatures of minimum 250°F (121°C) and must not have an R-value greater than 8 (typical
R-value for
2’’ [51mm] thick fiberglass insulation).
Warning,
Do not apply insulation on the control box, front access panel, heat sinks and filter of the CMU.
Surfaces that can be insulated
Surfaces that cannot be insulated
!