Operation Menus
This menu is accessible through normal operation mode using the TDF digital room sensor.
1. The Mode Selector jumper (JP1) of the
digital room sensor must be set to the “RUN” position (Operation Mode).
2. Press the
and
buttons simultaneously for 5 seconds. The
“Enter Password”
screen appears.
3. Enter the password within 1 minute by using the arrow keys to increase or decrease the value and the
and
buttons to
toggle between the digits.
a. Password
637
= Network Settings Menu
b. Password
757
= Configuration Menu
4. If
you enter the wrong password, the digital room sensor displays “
Eror
” and returns to Operation Mode. The digital room
sensor will return to normal mode if you navigate through the entire menu and do not make any selection, or if you do not press
any key for 5 minutes. The changed values will be saved automatically.
Menu 637
– Network Settings
End
(exit menu)
bAC
(BACnet)
mOd
(Modbus)
Network
= scroll menu items
Exit menu and ret urn
to normal operation
0153000
0
(device instance)
MAC Address
0
(0-254)
MAX Master
127
(1-127)
Returns to run mode
DEVICE INSTANC IS NEXT
Go
COMM TIMEOUT
900 min
(15-1800 min)
COMPORT CONFIG
NP2s
(no parit y, 2 stop bit s)
ADDRESS
1
(1-246)
Returns to run mode
EP1s
(even parity, 1 stop bit)
OP1s
(odd parity, 1 stop bit)
*** To save any changes, press on TDF ***
*** To return to the previous step without saving, press on TDF ***
AV.45
KBAUD RATE
= select / set value
Auto
9.6
(9600)
19.2
(19200)
38.4
(38400)
57.6
(57600)
76.8
(76800)
DipS
(DI P switch)
KBAUD RATE
= select / set value
Auto
9.6
(9600)
19.2
(19200)
38.4
(38400)
57.6
(57600)
76.8
(76800)
DipS
(DI P switch)