![Neptronic CMU Series Скачать руководство пользователя страница 14](http://html.mh-extra.com/html/neptronic/cmu-series/cmu-series_specification-and-installation-instructions_1667972014.webp)
Compact Make-up Air Unit
Specification and Installation Instructions
www.neptronic.com
Page | 14
Outputs
– Menu Overview (2 of 3) | AO1, AO2, BO1 and BO2
Ctrl
(Control)
Out
P
(Outputs)
Main Menu
INPt
(Inputs)
Main Menu
= scroll menu items
= scroll menu items
Sub Menu
Configuration
BO1
AO2
OUTputs
AO1
BO2
DMPR
(damper)
FAN
(exhaust fan)
AO1 MODE
OFF
= select / set value
AO1
FAN MAX VOLT
AV.19
10V
(0-10V)
FAN DELAY SECONDS
AV.17
2 sec
(1-255 sec)
FAN MIN VOLT
AV.18
0V
(0-10V)
DAMPER DELAY SECONDS
AV.20
2 sec
(0-255 sec)
Go to "AO2"
DMPR
(damper)
FAN
(exhaust fan)
AO2 MODE
OFF
= select / set value
AO2
FAN MAX VOLT
AV.19
10V
(0-10V)
FAN DELAY SECONDS
AV.17
2 sec
(1-255 sec)
FAN MIN VOLT
AV.18
0V
(0-10V)
DAMPER DELAY SECONDS
AV.20
2 sec
(0-255 sec)
Go to "BO1"
DMPR
(damper)
FAN
(exhaust fan)
BO1 MODE
OFF
= select / set value
BO1
FAN DELAY SECONDS
AV.17
2 sec
(1-255 sec)
DAMPER DELAY SECONDS
AV.20
2 sec
(0-255 sec)
Go to "BO2"
Go to "BO2"
DMPR
(damper)
FAN
(exhaust fan)
BO2 MODE
OFF
= select / set value
BO2
FAN DELAY SECONDS
AV.17
2 sec
(1-255 sec)
DAMPER DELAY SECONDS
AV.20
2 sec
(0-255 sec)
Go to "Ctrl"
Go to "Ctrl"
Go to "BO2"
Go to "Ctrl
0-10
(Vdc Sensor)
AO1 SIGNAL RANGE VOLT
MSV.15
2-10
(Vdc Sensor)
0-10
(Vdc Sensor)
AO2 SIGNAL RANGE VOLT
MSV.16
2-10
(Vdc Sensor)
Go to "BO1"
*** To save any changes, press on TDF ***
*** To return to the previous step without saving, press on TDF ***
MSV.8
MSV.9
MSV.10
MSV.11
Go to "BO1"
Go to "AO2"
Go to "AO2"
Содержание CMU Series
Страница 19: ...Notes ...