CHAPTER 2 TROUBLESHOOTING
Fault Diagnosis and Troubleshooting
NEAX2000 IVS
2
Maintenance Manual
ND-70926 (E), Issue 3.0
Page 79
12
CS/ZT Fault
occurred
Fault Kind 05:
SYS-ID upload
failure
Check the LEN No. of the CS/
ZT with SYS-ID is correct by
CMAE YY=00>02
Make the CS/ZT Make busy
or Make idle condition by
CME5 Y=3.
Turn ON • OFF the CS/ZT
power switch.
Fault Kind 06:
SYS-ID download
failure
When input the SYS-ID from
MAT, check if the number is
correct.
Check the CS/ZT is CS/ZT
without SYS-ID
Make the CS/ZT Make busy
or Make idle condition by
CME5 Y=3.
Turn ON • OFF the CS/ZT
power switch.
Table 2-3 Remedial Action on Each Fault Kind (Continued)
FAULT
KIND
NUMBER
FAULT CONTENT
FAULT INFORMATION
REMEDIAL ACTION