below which the heater turns on. This gives an additional tolerance for the hot and cold 
water to mix in the middle of the water heater and only after the water is really cooled, the 
electrical heater turns on. This earns more time for the solar installation to heat up the water 
if there is enough energy.

Turning the water heater on

When the water heater is off and the controller's screen is in Design I view, by pressing the F button 
(On/Off/Set) the water heater turns on, the screen's brightness gets increased and the screen view 
goes to Design II.

If the requirements for heating up the water heater are implemented, all of the allowed heat sources 
will be activated (see Configuration of the allowed for use heat sources). The requirements for 
heating up are as follows:

For the 

solar collector's

 installation: the solar collector's circulation pump turns on if  

t1

 

or 

the temperature of the collector (t3) is higher than the temperature in the middle of the water 
heater (t5) with as many degrees as it is set in the menu 

Dif Temp 1,

  line 

Pump On

.  

The 

pump works until 

t1

 

gets less or equal to the degrees set in the menu 

Dif Temp 1,

 line 

Pump 

Off.  

While   this   installation   is   working,   an   animated   spinning   of   the   solar   installation's 

circulation pump (the upper one) appears on the display.

For the 

boiler's

 installation:

DHW priority 

mode 

 boiler's circulation pump turns on if 

t2

 

or the temperature of the 

boiler 

t4

 has to be higher than the temperature in the top section of the water heater 

t2 

with as many degrees as it is set in the menu 

Dif Temp 2,

 line 

Pump On

The pump works 

until  

t2

 

gets less or equal to the degrees set in the menu  

Dif Temp  2,

  line 

Pump Off. 

While this installation works, an animated spinning of the boiler installation's circulation 
pump (the bottom one) appears on the screen;

CH priority 

mode –

 

boiler's circulation pump turns on if its temperature (

t4) 

gets higher 

than the temperature set in the menu 

CH Setup,

 line 

Pump On. 

The pump turns off when 

t4

 gets lower than the temperature set in the menu 

CH Setup,

 line 

Pump Off. 

While this 

installation is working, an animated spinning of the boiler's installation circulation pump 
(the bottom one) appears on the display.

For the 

electrical heater

:

the electrical heater turns on when the temperature  

t5  

in the middle of the water 

heater gets below the limit set in the menu 

EL Eco Settings,

 line 

Heater On 

and turns 

off when the temperature

  t1

 in the bottom section of the water heater gets equal or 

NHC-H42-2 Reference Manual ver 1.6

стр. 7 / 18

Information about

the solar installation

Information about

the boiler installation

Information about the

heater's work mode and

the following turning On/Off

Moving bubbles indicate

the working heater

Содержание NHC-H42-2

Страница 1: ...ller has a contrast LCD display four control buttons and a LED indication for the electrical heater NHC H42 has a built in electronic temperature regulator to control a mono phase or three phase elect...

Страница 2: ...t day Prevents the freezing of the water heater or of the solar collector Information about the condition of the anode protector Information if higher than 30mA leakage from the electrical heater to t...

Страница 3: ...an electrical heater and two differential temperature regulators adapted for a solar collector installation and a heating installation with a boiler or a fireplace The difference in the differential t...

Страница 4: ...on the main screen The display has four main screen designs They show different screen view for the main work conditions of NHC H42 Water Heater Off Water Heater On Settings and Graphics 1 Design I Wa...

Страница 5: ...the temperature measured by the temperature sensor in the bottom section is displayed in this field Since the hot water goes up to the top section of the water heater and then to the pipes it is poss...

Страница 6: ...llation When the pumps are on and the differential temperatures t1 and t2 go below the limits set from the menu Dif Temp 1 2 line Pump Off the relevant circulation pump turns off To help the outer hea...

Страница 7: ...upper one appears on the display For the boiler s installation DHW priority mode boiler s circulation pump turns on if t2 or the temperature of the boiler t4 has to be higher than the temperature in t...

Страница 8: ...electrical heater is activated from the menu System Setting its turning on and off depends on the temperature in the bottom section of the water heater measured by Sensor 1 When changing the differen...

Страница 9: ...eater s control By pressing the View Enter button all the possible data appears successively in the following order Set temperature for heating with the electrical heater Temperature measured in the b...

Страница 10: ...heater It is broken or disconnected S1 E2 A breakdown in the temperature sensor in the bottom section of the water heater It is on short circuit S1 Frost On turning on the power the temperature of th...

Страница 11: ...oleness before turning it on again S5 E1 A breakdown in the water heater s middle temperature sensor It is broken or disconnected S5 E2 A breakdown in the water heater s middle temperature sensor It i...

Страница 12: ...r Changing the set temperature Further pressing any of the same buttons changes the set temperature in the relevant direction The View Enter button saves the new settings and the screen goes back to i...

Страница 13: ...the changes made on the current parameter Setting menus appear in the following order 1 Setting the temperature for turning on and off the electrical heater if it has been activated It turns on when t...

Страница 14: ...terval when the pump can turn on to transfer the heat energy to the solar collector on Holiday mode This interval must be during the night for this mode to make sense 9 Turns on off the anti frost saf...

Страница 15: ...stem Settings If you still have no boiler or solar installations you can deactivate them Moreover if you don t want the water heater to use electricity for the electrical heater you can disable it too...

Страница 16: ...reen view is in Design I press and hold for more than 2 seconds the F button to enter Settings mode menu Clear Errors By pressing the button select line Yes and press F again to save your choice and g...

Страница 17: ...ter heater s initial settings The temperature regulators NHC H42 are designed for different types of water heaters The necessary personalization is not made in the factory and after you instal your wa...

Страница 18: ...s to the next field of the same parameter by pressing button and it will start blinking increase the value of the blinking field by pressing the button and decrease it by pressing the button pressing...

Отзывы: