Code
(hex)
Additional
code
Meaning
Remedy
0C11
Device
number
The module is not located in the
configured slot. An active device was
inserted at the different location of the
physical bus structure after the
configuration frame was connected.
Check the configuration.
Adapt the configuration
frame if the modification
was done on purpose.
0C12
Device
number
The module is accessible but was not
put into operation due to missing
parameters. An active device was
replaced by an unknown device in the
physical bus structure after the
configuration frame was connected
(wrong instance ID).
Check the configuration.
Adapt the configuration
frame if the modification
was done on purpose.
0C13
Device
number
The process data length does not
correspond to the configured value.
The process data width of an active
device was changed after the
configuration frame was connected.
Check the configuration.
Adapt the configuration
frame if the modification
was done on purpose.
0C14
Device
number
The module type does not correspond
to the configured value.
Check the configuration.
Adapt the configuration
frame if the modification
was done on purpose.
0C15
Device
number
The module ID does not correspond
to the configured value.
Check the configuration.
Adapt the configuration
frame if the modification
was done on purpose.
20
|
ni.com
|
REM-11180 User Manual