Code
(hex)
Additional code
Meaning
Remedy
0A03
—
Memory problem (e.g., buffer too
small)
Restart the device.
Contact NI if the
problem persists.
0A04
—
Inconsistent parameters
Check the call.
0A05
—
Invalid parameters
Check the call.
0A06
—
Access not supported.
Check the call.
0A07
—
Object does not exist.
Check the call.
0A08
Code of failed
service
Maximum number of permitted
parallel SM services exceeded.
(Processing conflict)
Wait for the service
called previously to be
completed, and then try
again.
0A0C
Unknown
Variable_ID
Call of Set_Value or Read_Value
with a Variable_ID that contains
an unknown code.
Check the call.
0A0D
—
A firmware error occurred.
Restart the device.
Contact NI if the
problem persists.
0A18
Invalid
Used_Attributes
parameter
A reserved bit is set in
Used_Attributes.
Check the parameters.
0A19
Number of bus
devices
The end of the frame was
exceeded when accessing the
configuration or line 0 was
accessed.
Check the access.
0 A1 A
Invalid
Frame_Reference
(if specified)
The frame reference specified for
the service does not exist.
Check the parameters.
0A1C
Number of
connected devices
Maximum number of devices
exceeded.
Reduce the bus
configuration.
0A2F
—
Number of devices is zero.
Connect the device and
check the connection.
REM-11180 User Manual
|
© National Instruments
|
15