© National Instruments
|
5-25
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You also can specify the active edge of the Source input (rising or
falling).
Figure 5-26 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 5-26.
Single Pulse Generation
Single Pulse Generation with Start Trigger
The counter can output a single pulse in response to one pulse on a hardware Start Trigger signal.
The pulse appears on the Counter
n
Internal Output signal of the counter.
You can specify a delay from the Start Trigger to the beginning of the pulse. You also can specify
the pulse width. The delay is measured in terms of a number of active edges of the Source input.
You can specify a pulse width. The pulse width is also measured in terms of a number of active
edges of the Source input. You can also specify the active edge of the Source input (rising and
falling).
Figure 5-27 shows a generation of a pulse with a pulse delay of four and a pulse width of three
(using the rising edge of Source).
Figure 5-27.
Single Pulse Generation with Start Trigger
Pulse Train Generation
Refer to the following sections for more information about the cDAQ chassis pulse train
generation options:
•
•
Retriggerable Pulse or Pulse Train Generation
•
Continuous Pulse Train Generation
•
Buffered Pulse Train Generation
•
Finite Implicit Buffered Pulse Train Generation
S
OURCE
OUT
Co
u
nter Armed
S
OURCE
GATE
(
S
t
a
rt Trigger)
OUT