A-3
Hardware Problems
Cannot Drive Isolated Outputs
Verify that you have power connected to the V
ISO
and C
ISO
inputs on the NI CVS-1459RT
isolated power connector and that the contact at the screw terminals is solid. Because these
outputs are electrically isolated from the NI CVS-1459RT device main supply, they require
power in addition to the NI CVS-1459RT main supply.
Runaway Startup Application
If a runaway startup application causes the NI CVS-1459RT to become unresponsive, power off
the NI CVS-1459RT and then restart it in safe mode. Restarting the NI CVS-1459RT in safe
mode does not launch the embedded LabVIEW Real-Time engine.
LED Error Indications
The NI CVS-1459RT indicates specific error conditions by flashing the STATUS LED a
specific number of times. Refer to
, for the STATUS LED indications.
PWR/FAULT LED Is Not Lit When the NI CVS-1459RT
is Powered On
If the system power supply is properly connected (polarity is not reversed) to the
NI CVS-1459RT, but the PWR/FAULT
LED does not light up, check that the power supply is
within the specifications outlined in the
NI CVS-1459RT Specifications
. Using a power supply
that is not within these specifications might result in an unresponsive or unstable system and
could damage the NI CVS-1459RT.
If the BIOS setting
Restore After Power Loss
is set to
Stay Off
, the NI CVS-1459RT may be
powered, but turned off. Press the RESET button to power on the device.