What to Use

Ring lug

Wire, 1.3 mm

2

 (16 AWG) or larger

Screwdriver, Phillips #2

What to Do

Complete the following steps to ground the cRIO-9039.
1.

Attach the ring lug to the wire.

2.

Remove the grounding screw from the grounding terminal on the cRIO-9039.

3.

Attach the ring lug to the grounding terminal.

4.

Tighten the grounding screw to 0.5 N · m (4.4 lb · in.) of torque.

5.

Attach the other end of the wire to the grounding electrode system of your facility using a
method that is appropriate for your application.

Caution

 

If you use shielded cabling to connect to a C Series module with a plastic

connector, you must attach the cable shield to the chassis grounding terminal using
1.3 mm

2

 (16 AWG) or larger wire. Attach a ring lug to the wire and attach the wire

to the chassis grounding terminal. Solder the other end of the wire to the cable
shield. Use shorter wire for better EMC performance.

For more information about ground connections, visit 

ni.com/info

 and enter the Info Code

emcground

.

Connecting the cRIO-9039 to Power

The cRIO-9039 requires a 9 V to 30 V external power supply. The cRIO-9039 filters and
regulates the supplied power and provides power for the C Series modules. The cRIO-9039
has a primary power input, V1, and a secondary power input, V2.

The POWER LED on the cRIO-9039 indicates which power input is in use, as shown in the
following table.

Table 2. POWER LED Indicators

LED Color

LED Pattern

Indication

 

 

 

Green

Solid

The cRIO-9039 is powered from the V1 input.

Yellow

Solid

The cRIO-9039 is powered from the V2 input.

Off

The cRIO-9039 is powered off.

Caution

 

Do not connect V2 to a DC mains supply or to any supply that requires a

connecting cable longer than 3 m (10 ft). A DC mains supply is a local DC
electricity supply network in the infrastructure of a site or building.

8

  | 

ni.com

  | 

NI cRIO-9039 Getting Started Guide

Содержание cRIO-9039

Страница 1: ...document describes how to begin using the NI cRIO 9039 and NI cRIO 9039 Sync In this document the NI cRIO 9039 and NI cRIO 9039 Sync are inclusively referred to as the cRIO 9039 For more information a...

Страница 2: ...been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components m...

Страница 3: ...Compatibility Guidelines This product was tested and complies with the regulatory requirements and limits for electromagnetic compatibility EMC stated in the product specifications These requirements...

Страница 4: ...Marine Applications Some products are Lloyd s Register LR Type Approved for marine shipboard applications To verify Lloyd s Register certification for a product visit ni com certification and search f...

Страница 5: ...ars damaged in any way 3 Unpack any other items and documentation from the kit Store the device in the antistatic package when the device is not in use Verifying the Kit Contents Verify that the follo...

Страница 6: ...ers February 2015 or later NI CompactRIO Device Drivers August 2016 or later For minimum software support information visit ni com info and enter the Info Code swsupport Installing C Series Modules Co...

Страница 7: ...n a nonhazardous location the cRIO 9039 can be powered on when you remove modules Connecting the cRIO 9039 The cRIO 9039 has the following connectors LEDs and buttons Figure 2 cRIO 9039 Front Panel 1...

Страница 8: ...wire to the cable shield Use shorter wire for better EMC performance For more information about ground connections visit ni com info and enter the Info Code emcground Connecting the cRIO 9039 to Power...

Страница 9: ...er supply to the cRIO 9039 1 Ensure that your power supply is powered off 2 Install the ferrite on the negative and positive leads of the power supply as shown in the following figure Figure 3 Install...

Страница 10: ...cRIO 9039 When you power on the cRIO 9039 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few...

Страница 11: ...system password Note The default username for the cRIO 9039 is admin There is no default password for the cRIO 9039 so you must leave the password field blank when logging in until you set a system pa...

Страница 12: ...odule Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install is correct 9 Click Next to start the installation 10 Click Fin...

Страница 13: ...System IP Configuration 1 Put the cRIO 9039 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds...

Страница 14: ...d RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold...

Страница 15: ...r longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9039 is in safe m...

Страница 16: ...software or in the absence of such license agreements the National Instruments Software License Agreement available at ni com legal at the time of purchase For a copy of the software licenses applicab...

Страница 17: ...your product supports calibration you can obtain the calibration certificate for your product at ni com calibration National Instruments corporate headquarters is located at 11500 North Mopac Express...

Страница 18: ...d third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the National Instruments global trade compliance pol...

Отзывы: