background image

Table 1. Hazardous Location Retention Accessories (Continued)

Port

Required Accessory

Part Number

 

 

 

Mini DisplayPort

Mini DisplayPort Cable Retention Bracket

156866-01

SD Card Slot

SD Door Kit

783660-01

Special Conditions for Hazardous Locations Use in Europe and
Internationally

The cRIO-9039 has been evaluated as Ex nA IIC T4 Gc equipment under DEMKO Certificate
No. 12 ATEX 1202658X and is IECEx UL 14.0089X certified. Each device is marked   II
3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -20 °C ≤
Ta ≤ 55 °C.

Caution

 

You must make sure that transient disturbances do not exceed 140% of

the rated voltage.

Caution

 

The system shall only be used in an area of not more than Pollution

Degree 2, as defined in IEC 60664-1.

Caution

 

The system shall be mounted in an ATEX/IECEx-certified enclosure with

a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.

Caution

 

The enclosure must have a door or cover accessible only by the use of a

tool.

Electromagnetic Compatibility Guidelines

This product was tested and complies with the regulatory requirements and limits for
electromagnetic compatibility (EMC) stated in the product specifications. These requirements
and limits provide reasonable protection against harmful interference when the product is
operated in the intended operational electromagnetic environment.

This product is intended for use in industrial locations. However, harmful interference may
occur in some installations, when the product is connected to a peripheral device or test object,
or if the product is used in residential or commercial areas. To minimize interference with
radio and television reception and prevent unacceptable performance degradation, install and
use this product in strict accordance with the instructions in the product documentation.

Furthermore, any changes or modifications to the product not expressly approved by National
Instruments could void your authority to operate it under your local regulatory rules.

Caution

 

To ensure the specified EMC performance, operate this product only with

shielded cables and accessories. The DC power input cables may be unshielded.

NI cRIO-9039 Getting Started Guide

  | 

© National Instruments

  | 

3

Содержание cRIO-9039

Страница 1: ...document describes how to begin using the NI cRIO 9039 and NI cRIO 9039 Sync In this document the NI cRIO 9039 and NI cRIO 9039 Sync are inclusively referred to as the cRIO 9039 For more information a...

Страница 2: ...been switched off or the area is known to be nonhazardous Caution Do not remove modules unless power has been switched off or the area is known to be nonhazardous Caution Substitution of components m...

Страница 3: ...Compatibility Guidelines This product was tested and complies with the regulatory requirements and limits for electromagnetic compatibility EMC stated in the product specifications These requirements...

Страница 4: ...Marine Applications Some products are Lloyd s Register LR Type Approved for marine shipboard applications To verify Lloyd s Register certification for a product visit ni com certification and search f...

Страница 5: ...ars damaged in any way 3 Unpack any other items and documentation from the kit Store the device in the antistatic package when the device is not in use Verifying the Kit Contents Verify that the follo...

Страница 6: ...ers February 2015 or later NI CompactRIO Device Drivers August 2016 or later For minimum software support information visit ni com info and enter the Info Code swsupport Installing C Series Modules Co...

Страница 7: ...n a nonhazardous location the cRIO 9039 can be powered on when you remove modules Connecting the cRIO 9039 The cRIO 9039 has the following connectors LEDs and buttons Figure 2 cRIO 9039 Front Panel 1...

Страница 8: ...wire to the cable shield Use shorter wire for better EMC performance For more information about ground connections visit ni com info and enter the Info Code emcground Connecting the cRIO 9039 to Power...

Страница 9: ...er supply to the cRIO 9039 1 Ensure that your power supply is powered off 2 Install the ferrite on the negative and positive leads of the power supply as shown in the following figure Figure 3 Install...

Страница 10: ...cRIO 9039 When you power on the cRIO 9039 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few...

Страница 11: ...system password Note The default username for the cRIO 9039 is admin There is no default password for the cRIO 9039 so you must leave the password field blank when logging in until you set a system pa...

Страница 12: ...odule Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install is correct 9 Click Next to start the installation 10 Click Fin...

Страница 13: ...System IP Configuration 1 Put the cRIO 9039 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds...

Страница 14: ...d RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold...

Страница 15: ...r longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9039 is in safe m...

Страница 16: ...software or in the absence of such license agreements the National Instruments Software License Agreement available at ni com legal at the time of purchase For a copy of the software licenses applicab...

Страница 17: ...your product supports calibration you can obtain the calibration certificate for your product at ni com calibration National Instruments corporate headquarters is located at 11500 North Mopac Express...

Страница 18: ...d third party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the National Instruments global trade compliance pol...

Отзывы: