Installer level
: Allows editing the parameters related to pump operation in the hydraulic system on which it is
installed.
Password 1, default 001.
•
Advanced level
: Allows editing the parameters that so critical that they may compromise the life of the device,
the pump, and the system if they are set incorrectly.
Password 2, default 002
.
Within each menu, it is possible to change the relative access password.
NOTE
When an incorrect password is entered to access both the installer and advanced level, the parame-
ters can only be displayed but not edited.
In case of loss of the password, contact the technical support service to obtain the universal pass-
word.
Menu
Description
Level
Default
password
Control parameters
Menu of parameters for controlling the pump in the hydraulic system in
which it is installed.
Installer
001
Motor parameters
Menu of parameters for motor control
Advanced
002
IN/OUT parameters
Menu of parameters for analog and digital inputs and outputs
Installer
001
Connectivity parameters
Menu of parameters for connectivity and external communication.
Installer
001
9.6. Control parameters
Parameter
Default
Description
1
2
3
4
5
6
Control mode
1. Constant value
2. Fix speed
3. Constant value 2 set
4. Fix speed 2 values
5. External speed
6. MPPT
MPPT
The following control modes can be selected:
1. Constant value: the device varies the speed of the pump in
such a way as to keep the set value constant regardless of
water consumption.
2. Fix speed: the device powers the pump at the set frequen-
cy.
3. Constant value 2 set: two desired values can be selected
by opening or closing digital input 2.
4. Fix speed 2 values: two desired frequency values can be
selected by opening or closing digital input 2.
5. External speed: it is possible to control the motor frequen-
cy through an analog signal connected to analog input 4.
6. MPPT: the device varies the speed of the pump to maxi-
mize the power obtained from the photovoltaic panels.
x
x
x
x
x
x
Control mode aux
XXXXXXXX
Operate on digital input 4 to switch from the main control mode
to the auxiliary control mode and vice versa.
x
x
x
x
x
x
Max alarm value
p = XX.X [bar]
10
Value that can be reached in the system beyond which, even
in constant frequency operating mode, the pump is stopped
and an alarm signal is emitted. The pump is restarted only
after the measured value has dropped below the maximum
alarm value for more than 5 seconds.
x
x
x
x
x
x
Min alarm value
p = XX.X [bar]
0
Minimum value that can be reached in the system below
which, even in constant frequency operating mode, the pump
is stopped and an alarm signal is emitted. The pump is restar-
ted only after the measured value has risen above the mini-
mum alarm value for more than 5 seconds.
x
x
x
x
x
x
Open circuit voltage PV
V = XXX [VDC]
Open circuit voltage of the string of photovoltaic panels.
x
MPPT: voltage gap
dV = XXX.X [V]
Voltage range used in the MPPT control algorithm.
x
MPPT: time gap
dt = XX.X [s]
Time interval used in the MPPT control algorithm.
x
MPPT: frequency gap
df = XXX.X [Hz]
Frequency range used in the MPPT control algorithm.
x
SUND
22