• YELLOW flashing: alarm condition.
4. START / STOP: motor start / stop
5. DISPLAY
Keep the START / STOP key pressed down for at least 5 seconds to activate the START/STOP key lock function
through which it is only possible to scroll and view the operating parameters, using the + and - keys; this does not
allow starting or stopping the motor. Press the START/STOP button again for at least 5 seconds to deactivate the
lock.
Keep the + and - keys pressed for at least 5 seconds to reverse the display.
9.3. Control via App
The device can be controlled using a smartphone or tablet equipped with Bluetooth BTLE connectivity and with the
App Nastec NOW installed. The App is available for Android and iOS and may be downloaded, free of charge, from
the respective online stores.
Through the application it is possible to:
• Monitor multiple operating parameters simultaneously.
• Obtain energy consumption statistics and check alarm history.
• Run reports with the possibility of adding notes, images and send them by e-mail or store them in the digital
archive.
• Create schedules, save them in the archive, copy them to other devices, and share them among multiple users
• Control a device remotely, via Wi-Fi or GSM, using a smartphone placed nearby as a modem.
• Access manuals and additional technical documentation.
• Receive online help on parameters and alarms.
9.4. Initial display
When the device is switched on, the control firmware version (LCD = X.XX), the power firmware version (INV =
X.XX) and the hardware version (HW = X.XX) are communicated to the user.
Next, the initial view opens.
3.0
3.0
bar
bar
1
2
5
6
A01
A01
W01
W01
7
8
3
4
1: Bluetooth on. Flashing during communication; 2: Motor running; 3: Motor stopped; 4: Stand-by; 5: Value read; 6:
Units of measurement; 7: Alarm; 8: Warning
Parameter
Description
XX.X [bar]
Measured pressure value.
XXX.X [Hz]
Frequency with which the inverter is powering the motor.
XXX [VAC]
Inverter power supply voltage. This appears only while the motor is in the OFF state. In the ON state,
the current absorbed by the motor is displayed instead of the supply voltage.
XX.X [A]
Current absorbed by the motor.
X.XX [cosø]
Cosine of the ø phase displacement angle between voltage and current. It is also called the motor
power factor.
XX.X [kW]
Estimate of the active electrical power absorbed by the motor.
X [INV]
Device address when COMBO functionality is enabled.
AXX
Alarm XX.
WXX
Warning XX.
The App allows monitoring other parameters and consult the alarm log.
9.5. Menu
Access to the menus is password-protected at two levels:
SUND
21