11.2.2. Electrical connections.
S1+ S1- G
COMBO
MASTER: 0
S1+ S1- G
COMBO
SLAVE: 1
SLAVE: N
S1+ S1- G
COMBO
WARNING
Respect the polarity of the connections.
11.2.3. Programming the master unit.
Menu
Parameter
Value
Control parameters
COMBO
ON to activate.
Control parameters
Address
00
Control parameters
Alternance
ON to activate / OFF to deactivate.
Control parameters
Alternance period
Establishes the number of hours of continuous operation after which the pumps in the
unit are forced to alternate. The value 0 means 5 minutes.
Control parameters
Start delay AUX
We recommend setting 0 s.
IN/OUT parameters
Min start irradiation
In COMBO Solar operating mode with solar meter connected, it specifies the addition-
al irradiation value to the irradiation specified by the parameter Min stop irradiation
necessary to start another pump in sequence. It is advisable to set this parameter
equal to the irradiation value necessary for the operation of a pump in the group at
maximum power increased by 10%.
11.2.4. Programming of slave units.
Menu
Parameter
Value
Control parameters
COMBO
ON to activate.
Control parameters
Address
from 01 to 07.
Control parameters
Alternance
ON to activate / OFF to deactivate. It is possible to determine which devices are
included in the alternation and which are not. Devices excluded from the alternation
will receive a starting priority based on their address.
NOTE
To start or stop a unit in COMBO mode, simply press the START or STOP button on the master unit
only.
NOTE
To change the operating parameters of a COMBO unit, operate on the unit's master.
When the Master Menu is exited, the remote programming of the connected slave units is required.
In this manner, all parameters set in the master are also copied to the slaves with the exception of
parameter Address.
SUND
30