○ For installations on combustible flooring an ember stop protective floor covering must be installed.
○ An ember stop of minimum 0.015" (0.4mm) thick sheet steel extending 18" (457mm) in front of firebox door
to 2” (76mm) behind the cleanout of the chimney. The ember stop width must protrude a minimum of 8”
(203mm) from both sides of the furnace.
○ Carpet or other floor covering shall be removed before placement of ember stop sheet.
○ Refer to Section 7.1 of CAN/CSA-B365-01 for complete details of floor protection.
6.6 EmBEr STOP
SamPleS of allowable Plenum/duCTinG arranGemenTS ConTinued
EMBER STOP
8"
(203mm)
EMBER STOP: SIDE DIMENSIONS
8"
(203mm)
18"
(457mm)
EMBER STOP: FRONT AND REAR DIMENSIONS
EMBER STOP
2"
(51mm)