W415-1013 / B / 07.24.13
37
EN
•
stand alone wood furnace
•
combination wood/oil furnace
ventIng cOnFIguRatIOn FOR BRIngIng sepaRate WOOD anD OIl FuRnace Flues IntO a cOMMOn vent
1
2
3
4
11
10
9
8
7
6
5
12
1
2
3
4
10
9
8
7
6
5
11
12
LEFT hANd RA CoNFIgURATIoN
RIghT hANd RA CoNFIgURATIoN
6.0 PLENum ANd vENTING INSTALLATION/
CLEArANCE TO COmBuSTIBLE mATErIALS
6.1 FLuE / CHImNEy FOr HmF150/200 IN CONFIGurATIONS
•
use of inclined manual dampers are forbidden.
•
barometric dampers can be installed to maintain normal operating draft between 0.04” and 0.06” w.C
(10 Pa and 15 Pa).
•
combination wood/electric furnace
•
combination wood/electric/oil furnace
legend
(ITEMS 1 THROUGH 11 BY INSTALLER)
1.
vent/chimney in accordance with Can/
CSa-b365-01, CSa b139-09, nfPa211,
construction and installation by qualified licensed
installer
2.
7” (178mm) T
3.
6” to 7” (152mm to 178mm) increaser
4.
6” (152mm) T
5.
6” (152mm) end cap for clean out
6.
5” to 7” (127mm to 178mm) increaser
7.
90° 5” (127mm) elbow
8.
barometric damper
9.
45° 5” (127mm) elbow (change angle to suit
incline)
10.
WARNING: Oil flue to be mounted on same side
of furnace as blower box, to respect clearance to
combustible dimensions.
11. 90° 5” (127mm) elbow (offset in two directions)
12. Heat shield
6.1.1 CONTrOLLING drAFT
6.2 vENTING CONFIGurATION FOr wOOd/OIL COmBINATION FurNACE
h3.53
all plenuM DuctIng anD ventIng InstallatIOn Must cOnFORM WItH can/csa B365-01,
csa B139-09, anD nFpa 211. alWaYs cHeck lOcal BuIlDIng anD FIRe cODes , anD autHORI-
TIES hAvINg jURISdICTIoN.
all plenuM, DuctIng anD ventIng Must Be InstalleD BY a QualIFIeD/lIcenseD Install-
ER.
DO nOt use MakesHIFt cOMpROMIses DuRIng InstallatIOn. DO nOt BlOck OR RestRIct
aIR. DO nOt IMpeDe aIR MOveMent In zOnes MaRkeD "cleaRance tO cOMBustIBles".
MInIMuM cleaRance tO cOMBustIBle DIMensIOns Must Be IMpleMenteD.
h3.54
do NoT CoNNECT ThIS UNIT To A ChIMNEy FLUE SERvINg ANoThER AppLIANCE!!
tHe WOOD FuRnace sectIOn can OpeRate usIng a MInIMuM 6" (152
mm) Ø
Flue pIpe, But
We RecOMMenD tHat tHe Flue sIze Be set at a MInIMuM OF 7" (178
mm) Ø WhERE ThE FUR-
nace Is tO Be set up as (OR In cOnsIDeRatIOn tO a FutuRe RetRO FIt tO a WOOD/OIl OR
WOOD/OIl/electRIc cOMBInatIOn.
use cHIMneY ceRtIFIeD tO 2100°F (1149°c) FOR WOOD BuRnIng applIances, lIsteD as
ul103Ht(usa), ulcs629 (canaDa) MInIMuM 6” (152
mm) dIAMETER LISTEd RESIdENTIAL ChIM-
NEy. SEE ANd FoLLoW ChIMNEy MANUFACTURES INSTRUCTIoNS.
cHIMneY DRaFt gReateR tHan -0.06” W.c. (-15 p
a
) MaY cause an uncOntROllaBle FIRe
ANd dAMAgE ThE FURNACE.