23
System Troubles
Use the System Trouble chart on the following
page to determine the specific System Trouble
(s).
During normal panel operation the
H
SYSTEM
TROUBLE LED has the following two modes of
operation:
STEADY
1-7 possible trouble
groups, AC is present
FLASHING
1-7 possible trouble
groups, AC is not present
Viewing System Trouble(s)
Press the
A4
key on the keypad.
To determine the System Trouble Group Num-
ber, count the number of times the
H
SYSTEM
TROUBLE LED blinks. The keypad sounder will
beep at the same rate that the
H
SYSTEM
TROUBLE LED blinks.
To determine the System Trouble, note the
zone LED that is ON. Look up the specific sys-
tem trouble on the chart on the following page.
The
H
SYSTEM TROUBLE LED and keypad
sounder will continue to flash and beep. To view
the next System Trouble, if any, press the
E
key. Continue pressing the
E
key, if there are
no more system troubles to view, the system will
return to normal operation.
Note:
System Troubles Groups 3 through 7 -
System Trouble Groups that have a zone or
smoke detector associated with the trouble,
such as RF low battery. The zone(s) of the de-
vice with a low battery will be displayed by the
ZONE LED . For example, a wireless low battery
on zone 2 would beep the keypad sounder 3
times and turn on zone 2 LED.
Audible System Trouble Indication
- For all
system troubles, except when the only system
trouble is the loss of AC, the keypad will beep
once every 10 seconds. The keypad will con-
tinue to beep until the reset button is pressed or
the trouble has been acknowledged by pressing
the
C
key.
System Trouble Reporting
The following system troubles, when enabled to
report to Telco 1 [37-3] or Telco 3 [57-3], will
send the report code programmed in Trouble
Report [63] if reporting using a pulse format:
System Trouble Pulse Report Code
Bell Cut F1
2-Wire Fire Trouble F1
Rcvr Fail-to-Respond F1
Receiver Tamper F1
Receiver JAM F1
Tx Low Battery F1
Tx Supervisory Failure F1
If reporting using Point ID, a unique code will be
sent for each of the following System Troubles.
System Trouble Point ID Report Codes
Bell Cut CODE 1 321 G00 ZN000-BELL 1 TROUBLE
2-Wire Fire Trouble CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
Rcvr Fail-to-Respond CODE 1 382 G00 ZN000-SENSOR TROUBLE
Receiver Tamper CODE 1 145 G00 ZN000-EXP. MODL. TAMPER
Receiver JAM CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
A
300
(SYSTEM TROUBLE RST) code is sent if a restore is
reported after multiple troubles.
System Trouble
Group #
Keypad SYSTEM Trouble
LED is flashing 1 time
indicating System Trouble
Group 1.
Keypad Sounder beeps 1
time indicating System
EXAMPLE
-
LOW
BATTERY
SYSTEM
TROUBLE
DIS-
PLAY
Zone LED(s)
is ON
indicates
(Specific Trouble)
Specific Trouble
Zone 2 LED is ON indicating
Low Battery. (1 Beep, LED 2)
Flashing
(System Trouble
Group Number)
Enter
A4
to enter System Trouble mode
and determine the specific trouble. Press any key to
view all system troubles.
ARM
ED
H
G EM I N I
2
STA
TUS
Beeping
(System Trouble
Group Number)
FIGURE
9
S
YSTEM
T
ROUBLE
E
XAMPLE
Содержание GEM-P800
Страница 1: ...WI850E 04 10 NAPCO 2010 GEM P800 Control Panel Communicator Installation Instructions ...