![NAPCO GEM-P800 Скачать руководство пользователя страница 22](http://html1.mh-extra.com/html/napco/gem-p800/gem-p800_installation-instructions-manual_3286274022.webp)
WI850D GEM-P800 Installation Instructions
22
TEM TROUBLE LED, including Fire Trou-
ble. If required Fire Trouble can be dis-
played on the Fire LED. Fire Trouble is indi-
cated by a steady
I
Fire LED.
[97] Dealer Options 2
(1) International Dialing Protocol
- No
dialing if no dial tone, 60 s between attempts
and 4 s wait for dial tone.
(2) Invert Bell Output
- Inverts the Bell
polarity and removes supervision from the
bell circuit.
(3) System Trouble Auto Restore
- Nor-
mally, System troubles require acknowledg-
ment (View System Trouble) in order to re-
store. If this option is selected troubles will
restore without requiring acknowledgment.
(4) User 1 Code-Program only
- If en-
abled User 1 Code will function only as the
User Program Code and will not Arm/Disarm
the panel.
Note: All programming within Programming
Blocks [96] & [97] will not change if the
panel is defaulted.
[98] Number of Re-Dials
The Number of re-dial attempts made by the
panel before indicating a
Fail-to-
Communicate
(System Trouble 1-3).