INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS
FIRE PUMPS - NF-VTP SERIES
Ref. No. NFVTP-IOM/
2016
/V.
02
SL. NO
DESCRIPTION
RESULT
15
Cooling system from heat exchanger or cooling water supply pipe line
from pump discharge is installed (Engine).
Yes
£
No
£
16
Cooling line return line one size higher than inlet and this return water
should be visible to monitor.
Yes
£
No
£
17
Diesel tank located above ground (Outlet of diesel tank should be above
or same level of diesel engine inlet).
Yes
£
No
£
18
Fuel pipe lines are installed correctly with all necessary fittings.
19
Water supply to the fire pump adequate to meet fire pump requirements
and Local Civil Defense.
Yes
£
No
£
20
Automatic air release valve.
Yes
£
No
£
21
Offset and operating angles for drive shaft meets manufacturer’s
instructions.
Yes
£
No
£
22
The surface of the foundation must be completely horizontal and
perfectly flat.
Yes
£
No
£
23
The foundation should be
200
mm larger than the base frame on all four
sides.
Yes
£
No
£
24
Flow meter upstream and down stream consider as per manufacturer’s
recommendation.
Yes
£
No
£
25
Pump discharge head base and horizontal driver base grouting had
penetrated to the required areas to form a rigid foundation
Yes
£
No
£
26
Discharge pipes are provided with proper support to avoid strain on
pump.
Yes
£
No
£
27
Right angle gear drive is properly aligned with the pump top shaft
Yes
£
No
£
28
Stuffing box cooling lines are connected properly to discharge line and
disposal area
Yes
£
No
£
29
Wiring between drivers, controllers and power supply is done as per
manufacturer’s wiring / connection diagrams.
Yes
£
No
£
30
Drive shaft guard and pump stuffing box guard are fixed.
Yes
£
No
£