Fault
Remedy
?
Electrical circuit open or not
completed.
Check circuit and correct
accordingly.
?
Low voltage supply to electric
driver.
Check whether driver wiring is
correct and receiving full voltage.
? ? ?
Speed is too low.
Check if driver is directly across the
line and receiving full voltage.
?
Defective motor.
Consult factory.
? ? ?
Wrong rotation.
Ensure that pump is rotating CCW
when viewed from above. Check
engagement of motor coupling.
?
Excessive horsepower
required.
Investigate and rectify the cause for
excessive horse power requirement.
?
Improper lateral adjustment.
Impeller binds against bowls.
Reset impeller adjustment.
? ?
Impellers adjusted too high.
Adjust impellers.
? ?
Closed discharge valve.
Fully open the discharge valve.
? ? ? ?
Obstruction in liquid passage.
Suction strainer clogged.
Pull pump, inspect suction strainer,
impeller and bowls.
? ? ?
Insufficient submergence of
pump bowls.
Lower pump if possible or adjust
water level in tank as necessary.
? ?
? ?
Cavitation.
Insufficient NPSH available.
Consider lowering the bowl
assembly by adding column.
10. FAULTS & REMEDIES