43
of
46
Subject to change without prior notice
INSTALLATION OPERATION AND MAINTENANCE INSTRUCTIONS
FIRE PUMPS - NF-VTP SERIES
Ref. No. NFVTP-IOM/
2016
/V.
02
Description
Visual
Inspection
Check Change Clean Test Frequency
Date
(g) Condition of flexible hoses and
connections
X
X
Weekly
(h) Jacket water heater
X
Weekly
(i) Inspect duct work, clean louvers
(combustion air)
X
X
X
Annually
(j) Water strainer
X
Quarterly
4
. Exhaust system
(a) Leakage
X
X
Weekly
(b) Drain condensate trap
X
Weekly
(c) Insulation and fire hazards
X
Quarterly
(d) Excessive back pressure
X Annually
(e) Exhaust system hangers and
supports
X
Annually
(f) Flexible exhaust section
X
Semiannually
5
. Battery system
(a) Electrolyte level
X
Weekly
(b) Terminals clean and tight
X
X
Quarterly
11. FIRE PUMP INSPECTION, TESTING AND MAINTENANCE SCHEDULE