(Revised 4-9-2013) NT24k Managed Industrial Ethernet Switch User Manual & Installation Guide Page 21 of 132
NT24k with AC Power Supply Installed:
Unscrew & Remove the AC Voltage Input
Plug from the Power Input Header
Install the AC Power Cables into the Plug
(observing polarity).
Plug the Voltage Input Plug back into the
Power Input Header.
Tightening torque for the terminal block
power plug is
0.5 Nm/0.368 Pound Foot.
Verify the Power LED stays ON.
When an AC Power supply is installed (i.e., the –AC option), Use 12-24 gauge wire when
connecting to the power supply.
NT24k Fault Pins
The Fault pins on the back of the NT24k can be used for an alarm contact. The current carrying capacity is
1A at 24VDC. It is normally open and the relay closes when a fault condition occurs, though this can be
reversed via configuration. These pins can be used to connect an external warning device such as a light in
order to provide an external alarm. The conditions for generating a fault condition (closing the relay) can be
configured through software.