7.13 MODULE OUTPUT CONFIGURATION
Index
Sub-Index
Name
Data Type
Byte
Bits
Description
2001
1
Mode 1A
4 bit
1
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off
Mode 1B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
2
Mode 2A
2
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 2B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
3
Mode 3A
3
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off
Mode 3B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
4
Mode 4A
4
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 4B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
5
Mode 5A
5
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 5B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
6
Mode 6A
6
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 6B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
7
Mode 7A
7
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 7B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
8
Mode 8A
8
1,2,3,4
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Mode 8B
5,6,7,8
Mode 0x0=disabled, 0x1=On/Off, 0x2=Data(0-4000), 0x3=Percent(0-1000 =
0-100.0%), 0x4=Amps(0-4000 = 0-4.000 amps)
Note: The Global Output Configuration must be zero for individual configuration.
OUTMODE#
Output Operation
Notes
0x0h
Disabled
0x1h
Digital ON/OFF
0x2h
Data (0 – 4000)
PWMx = 12 bits 0-4000, >4000=0
0x3h
Percent (0% – 100.0%)
PWMx = 12 bits 0-1000, >1000=0
0x4h
Amps (0.100A – 4.000)
PWMx = 12 bits 100-4000, >4000=0
0xFh
Not Used
Invalid Output Configuration