Configuration/settings
User manual 55170_hdb_en_13
54 / 145
IO-Link state
Read-only access to the IO-Link devices/ports.
Tab. 8-7: Submodules for IO-Link state
Submodules
Deactivated
The corresponding IO link port is marked as being de-
activated. However, the entry in "IO-Link master" is
decisive for the actual configuration of the IO-Link de-
vice.
IOL_I/O_SI
0 bytes In, 0 bytes Out
IO link standard IO mode.
The channel is addressed as digital IO.
The data are read via "Digital IO".
However, the entry in "IO link master" is decisive for
the actual configuration of the IO link device.
IOL_I_x Byte
x bytes In
IO link device with x byte(s) input data.
The status can be identified via the corresponding bit
in "Qualifier DI".
It is possible to parameterize the diagnostics.
However, the entry in "IO link master" is decisive for
the actual configuration of the IO link device.
IOL_O_y Byte
y bytes In
IO link device with y byte(s) output data. The current
output data can be read as input data.
The status can be identified via the corresponding bit
in "Qualifier DO".
It is possible to parameterize the diagnostics.
However, the entry in "IO link master" is decisive for
the actual configuration of the IO link device.
IOL_I/O_x/y Byte
x + y bytes In
IO link device with x byte(s) input data and y byte(s)
output data.
The first x byte(s) are the current input data of the IO
link devices; the following y byte(s) are the current
output data of the IO link device.
The status can be identified via the corresponding bit
in "Qualifier DI" and "Qualifier DO".
It is possible to parameterize the diagnostics.
However, the entry in "IO link master" is decisive for
the actual configuration of the IO link device.