Configuration/settings
User manual 55170_hdb_en_13
116 / 145
Creating project 2
Setting PLC_2 access
1 |
Start another instance of the TIA portal.
2 |
Set up a new project with the name of “PLC_2“.
3 |
Add a controller.
4 |
Assign the name “PLC_2“ to the controller.
5 |
Copy the IMPACT67
module
from the first “PLC_1“ project and insert it in
the network view of the “PLC_2“ project.
6 |
Assign the IMPACT67
module
to the “PLC_2“
controller.
7 |
Select the IMPACT67
module
to navigate to the Shared Device menu
item
and
8 |
set access to the “PLC_2“ controller.
9 |
Then download the configurations to the corresponding controllers.
NOTE
The procedure described is needed to configure shared devices.
If necessary, as described in the manual:
Set parameters for the real-time settings to achieve error-free operation.
For further information, refer to chap. 3.2.4 "Shared Device"