3.5.1
Data storage mode
NOTE
The data storage mode is only available for devices that comply with IO-Link
specification V1.1 and higher.
The data storage mode offers scope for replacing IO-Link devices without
reconfiguration.
The IO-Link master or the IO-Link device saves the set device parameters
of the previous configuration.
In data storage mode, the parameter data storage facilities on IO-Link
master and IO-Link device are synchronized.
Following replacement of a device, the master writes the saved device pa-
rameters to the new device whenever the data storage mode is enabled in
the IO-Link master. The application can be started without reconfiguration.
Following replacement of an IO-Link master, the device writes the saved
device parameters to the new master whenever the "Save & Restore" data
storage mode is enabled in the IO-Link master. The application can be
started without reconfiguration.