Operation
User manual 55170_hdb_en_13
135 / 145
0x4500
(17664)
0x770D
(30477)
0x770D
(30477)
Cable break of the subordinate device 13
Check the installation.
0x4500
(17664)
0x770E
(30478)
0x770E
(30478)
Cable break of the subordinate device 14
Check the installation.
0x4500
(17664)
0x770F
(30479)
0x770F
(30479)
Cable break of the subordinate device 15
Check the installation.
0x4500
(17664)
0x7710
(30480)
0x7710
(30480)
Short Circuit
Check the installation.
0x4500
(17664)
0x7711
(30481)
0x7711
(30481)
Grounding error
Check the installation.
0x4501
(17665)
0x8000
(32768) –
0xFFFF
(65535)
Event from an IO-Link device that does not
support the Murrelektronik IO-Link integra-
tion.
The Extended Channel Error Type plus
0x8000 (32768) corresponds to the original
IO-Link event code.
0x4501
(17665)
0x0100
(256)
0x8100
(33024)
Communication monitoring: General error
Check the device.
0x4501
(17665)
0x0110
(272)
0x8110
(33040)
Process data monitoring: General error
Check the device.
0x4501
(17665)
0x0C00
(3072)
0x8C00
(35840)
Technology-specific error in the application Reset the device.
0x4501
(17665)
0x0C01
(3073)
0x8C01
(35841)
Simulation active
Check the operating mode.
0x4501
(17665)
0x0C10
(3088)
0x8C10
(35856)
Process value above the valid range
Process value uncertain
0x4501
(17665)
0x0C20
(3104)
0x8C20
(35872)
Exceeding of the measuring range
Check your application.
0x4501
(17665)
0x0C30
(3120)
0x8C30
(35888)
Process value below the valid range
Process value uncertain
0x4501
(17665)
0x0C40
(3136)
0x8C40
(35904)
Service requirement - cleaning
Clean the device.
0x4501
(17665)
0x0C41
(3137)
0x8C41
(35905)
Service requirement - topping up
Top up the device.
0x4501
(17665)
0x0C42
(3138)
0x8C42
(35906)
Service requirement - wear
Replace the wearing parts on the
device.
0x4501
(17665)
0x0CA0
(3232) –
0x0DFE
(3582)
0x8CA0
(36000) –
0x8DFE
(36350)
Device-specific error code
For further details of this IO-Link
event, please read the manual for
the IO-Link device.
0x4510
(17680)
0x0000 (0)
– 0x7FFF
(32767)
Event from an IO-Link device that supports
Murrelektronik IO-Link integration.
The Extended Channel Error Type corre-
sponds to the original IO-Link event code.
0x4510
(17680)
0x1000
(4096)
0x1000
(4096)
General malfunction
Unknown error
0x4510
(17680)
0x1800
(6144)
0x1800
(6144)
Production data invalid
Replace the device.
0x4510
(17680)
0x1801
(6145)
0x1801
(6145)
Parameter data invalid
Replace the device.
0x4510
(17680)
0x1802
(6146)
0x1802
(6146)
Process data area has dropped below its
lower warning threshold
The scanned process data value
is less than or equal to the lower
warning threshold setting.
0x4510
(17680)
0x1803
(6147)
0x1803
(6147)
Process data area has exceeded its upper
warning threshold
The scanned process data value
is greater than or equal to the up-
per warning threshold setting.
0x4510
(17680)
0x1804
(6148)
0x1804
(6148)
Sensor power supply overload
Check the installation. Check the
current input of the connected
consumer.
Channel
Error Type
Extended
Channel
Error Type
IO-Link
Event
code(s)
Meaning
Action