ComDry M160L

6.7 Navigate the menus

The three buttons

,

and

on the control panel make it possible to navigate the menus.

Follow these steps to navigate the menus:

Step

Action

Result/Illustration

1

To select a menu, press

or

. until the selected menu appears.

The selected menu indicator is lit.

2

To enter the menu, press

.

The menu indicator starts
flashing.

f

 

X

3

Use

or

to scroll through the menu.

4

Leave the menu by using

and go to

[

EXIT

]

.

Press

.

The menu indicator stops
flashing.

NOTE!

All menu lists are circular. At the end of each menu you will find

[

EXIT

]

. The quickest way of navigating

there is to press

one time after having entered a menu.

17

Operation

190TEN-1098-D1404

Содержание comdry m170l

Страница 1: ...Original instructions Usermanual ComDryM160L Desiccantdehumidifier 190TEN 1098 D1404 MuntersEuropeAB2014 ...

Страница 2: ... describedinsectionServiceandmaintenance Theservice andmaintenancemustbedocumentedforthewarranty tobevalid Safety Informationaboutdangersareinthismanualindicated bythecommonhazardsymbol W W WARNING ARNING ARNING Indicatesa possibledangerthatcanleadtopersonalinjury CA CA CAUTION UTION UTION Indicatesa possibledangerthatcanleadtodamagetothe unitorotherproperty orcauseenvironmentaldamage NOTE Highlig...

Страница 3: ...6 4 Stop the dehumidifier 16 6 5 Emergency 16 6 6 Automaticstart afterpower failure 16 6 7 Navigate themenus 17 6 8 Access thecontrol system 18 6 9 Change the system settings 19 6 10 Reset analarm 20 6 11 Reset thecounters 21 6 12 Service interval alarm 22 6 13 Restore the default settings 23 6 14 Access levels 23 7 Menusandparameters 24 7 1 Humidity 24 7 1 1 Internal controlling sensor 25 7 1 2 E...

Страница 4: ...ier is placed in a building with radon it is necessary to contact anexpert to secure the best overall solution Allchanges affecting the ventilation orthe pressurebalance in the building can result in a changed concentration of radon CA CA CAUTION UTION UTION Do not sit stand orplace any objects onthe unit 1 3 Safety Everymeasurehasbeentakeninthedesignandmanufactureofthedehumidifiertoensurethatitme...

Страница 5: ...ther mains voltage than specified onthe identification plate Do not operate the unit if the power plug orcordis damaged riskof electrical shock Do not pull the plug with wet hands riskof electrical shock Do not insert fingers orany other objects into the airvents rotating fans are inside Do not cover the unit as that can block airintake oroutlet and cause a fire If the unit has overturned cut the ...

Страница 6: ...Dry M160L 0 0 230V 50 60 Hz Made in Sweden Munters Europe AB Isafjordsgatan 1 164 26 Kista Sweden Weight 17 kg IP33 0 84 kW RoHS M Figure1 2Identificationplate anexample Explanationof Fabr No ontheidentificationplate 10 Yearofmanufacture 15 Weekofmanufacture 170XXX Articlenumber XXXXX Serialnumber 3 Introduction 190TEN 1098 D1404 ...

Страница 7: ...ly theincomingair alwaysmeetsadryzoneontherotor thuscreatingacontinuousdehumidificationprocess Theairflowthatisusedtodrytherotor reactivationair isheated Thereactivationairpassesthrough therotorintheoppositedirectiontotheprocessairandleavestherotoraswetair warmhumidair The wetairre circulatesthroughacondenserthatcoolsdowntheairtocondensethewaterusingapartofthe processair Thecondensedwaterisdischar...

Страница 8: ...ncludedandnothingisdamaged 2 ContactMuntersimmediatelyifthedeliveryisnotcompleteinordertoavoidinstallationdelays 3 Iftheunitistobeputintostoragepriortoinstallation seesectionStoringtheequipment 4 Removeallpackagingmaterialfromtheunit andmakesurethatnodamagehasoccurredduring transportation 5 AnyvisibledamagemustbereportedinwritingtoMunterswithin5daysandpriortoinstallationof theunit 6 Disposeofthepa...

Страница 9: ...cure the best overall solution Allchanges affecting the ventilation orthe pressurebalance in the building can result in a changed concentration of radon 4 2 Closedsystem Thedehumidifierisplacedinthespacetobedehumidified Toensurethatthedryairisdistributedevenly inthespacetobedehumidifiedaductingcanbeconnectedtothedryairoutletofthedehumidifier The condensedwaterisdrainedthroughahose Aclosedsystemisp...

Страница 10: ...dspace object 2 1 3 Com Dr y M 160L Figure4 2 Opensystemprinciple 1 Process Reactivationair 2 DryAir 3 Condensedwater 4 4 Siterequirements Thedehumidifierisonlyintendedforindoorinstallation Avoidinstallingthedehumidifierinadamp environmentwherethereisariskofwaterenteringtheunitorinaverydustyenvironment Ifindoubt seekadvicefromMunters Itisimportantthattheintendedinstallationsitemeetsthelocationands...

Страница 11: ... Laydownthedehumidifier 1 2 Figure4 3 Figure4 4 6 InserttheO ring 1 intothedrainpipesleeve 2 PresstheO ringsoitisproperlyseatedinthegroove seeFigure4 3 7 Pushthedrainpipeontothedrainconnectionofthetray seeFigure4 4 8 Fastenthedrainpipewiththetwoenclosedscrews 9 Therearetwoslotsintheshelfenablingalashingstraptobemountedifthedehumidifieristobefixed byastrap 10 Alternativelythefourfeetcanbelockedsimp...

Страница 12: ...ustbeairtightandvapourtighttoensurefullperformance Thetotalresistanceintheductworkmustnotexceedtheperformanceratingofthefansfittedinthe dehumidifier NOTE Maximumlength of dryairhose is 25metres 4 7 Connectingthedrainhose Beforeconnectingthedrainhosethedehumidifiermustbemountedonthewallusingtheenclosedwall bracket Theminimumdistancebetweenthebottomofthedehumidifierandtheflooris25cm Figure4 5Drainho...

Страница 13: ...pperpartoftheunit CA CA CAUTION UTION UTION Do not connect the unit to other mains voltage than specified onthe unit s identification plate Themainsfrequencycanbeadjusted seeTable7 5 NOTE In case of a fixed installation where the plug is replaced by a circuit breaker check that the fuse rating in the circuit breakeris correct 190TEN 1098 D1404 Installation 10 ...

Страница 14: ...puternetwork AllComDrydehumidifiersareequippedwithtwoCANBUSports locatedbehindacovernexttothe applianceinlet Anindoorremotecontrol externalhumidity temperaturesensorsoranexternalsignalbox canbeconnectedtotheseCANBUSports Itdoesnotmatterwhichoftheabovedeviceswillbeconnected towhichport Whennoportisusedthetwoemptyterminationplugsmustbefittedtotheports Figure4 6Removethecover Figure4 7 2CANBUSportswi...

Страница 15: ...saneedtoconnectaninletductorhosetothedehumidifier RemoteControlmakesitpossibletocontroltheunitfromdistance deliveredwitha10metrecable Externalsignalbox isusedwhenthereisaneedtoconnecttoanexternalcontrolsystem RemoteRH Tsensorforexternalmeasuringofhumidityandtemperature WallBracket StubPipeKit kWh C fX RemoteControl Externalsignalbox RemoteRH Tsensor 190TEN 1098 D1404 Installation 12 ...

Страница 16: ... 6 1 Humiditymenu 4 Temperaturemenu A Alarmindicator 2 Timemenu 5 Functionsmenu B Operationindicator 3 Powermenu 6 Alarmmenu C On Offbutton Menubutton Function Up Rightbutton Enter Confirmationbutton Down Leftbutton Table5 1Menubuttonfunctions 13 Controlpaneloverview 190TEN 1098 D1404 ...

Страница 17: ...hetemperaturesbeforeandafterthe heater aswellasinthewetairaftertherotor Ahighsafetylevelisobtainedbyvarioustemperaturesensors Toohightemperaturesgivesareductionoftheheaterpower whileexcessivetemperatureswillmakethe systemissueanalarmandshutthedehumidifierdowninacontrolledway Forfurtherexplanation see 7 1 Humidityand7 5 Functions NOTE Thedehumidifier always operates in automatic mode moisturebased ...

Страница 18: ...nish thebooting before attempting to start the dehumidifier 6 3 2 Startthedehumidifier Followthesestepstostartthedehumidifier Step Action Illustration 1 PresstheOn Offbutton C oncetostartthedehumidifier Result If themeasuredhumidityislowerthantheSetValue thegreenoperatingindicator B willstarttoflash ina long on shortoffsequence Dependingon fanmodesetting the processfanwillrunornot Theunit isnowins...

Страница 19: ... continuestorunfora whileinordertocooldownand thenstops 6 5 Emergency CA CA CAUTION UTION UTION Only quick stop the dehumidifier in the case of anemergency Thefan stops and theheater can bevery hot which can result in damage to the heater and other components close to it Incaseofemergency stopthedehumidifierbypullingthemainsplugor ifitispermanentlyconnected tomains byusingtheexternalswitch 6 6 Aut...

Страница 20: ...heselectedmenuappears Theselectedmenuindicatorislit 2 To enterthemenu press Themenuindicatorstarts flashing fX 3 Use or toscrollthroughthemenu 4 Leavethemenuby using andgo to EXIT Press Themenuindicatorstops flashing NOTE Allmenu lists arecircular Atthe end of each menu you will find EXIT Thequickest way of navigating there is to press one timeafter having entered a menu 17 Operation 190TEN 1098 D...

Страница 21: ...elexists If an attempt togethigheraccessismadewiththemachineswitchedoff thedisplaywill changeto 0 0 0 0 Press fourtimesuntil ACCESS isvisibleagain NOTE Thesystem will returnto locked mode automatically after five minutes without any activity NOTE Thesystem always starts in locked mode after power up orpower failure regardlessof access level priorto unplugging the unit Followthesestepstoforcethesys...

Страница 22: ... or 2 Press Thesettingstartstoflash 3 Changethevaluewith and 4 Confirmthenewsettingwith Thesettingstopstoflash NOTE If the new setting is not confirmedwithin 30seconds the display changes back to the old setting NOTE Read only values arenot changeable They will not start to flash if is pressed regardlessof access level To find out if a parameteris changeable orread only see section 7 Menus and par...

Страница 23: ...ing 2 Wait untilthedehumidifierhas stopped Press Thedisplaychangesto RstNO and NO isflashing C fX kWh fX Rst NO 3 Toggle NO to YES by pressingeither or Confirmbypressing Whenthealarmhasbeenreset themenu systemreturnstoitsstartposition NOTE If the cause of an alarmis still present the alarmmight bere issued after resetting even if the dehumidifier is stopped 190TEN 1098 D1404 Operation 20 ...

Страница 24: ...vigatethemenus 2 Press Thedisplaychangesto RstNO and NO isflashing C fX kWh fX Rst NO 3 Toggle NO to YES by pressingeither or NOTE If Rst NO Rst YES is left without action for30 seconds the display automatically changes back to thestored counter value 4 Confirmtheresettingwith Thecounterisreset NOTE PressingENTERwhen the display shows Rst NO will returnthe stored counter value in the display again...

Страница 25: ...rval has been adjusted TheTimetoservicecounter Sxxxxh countsdowntozero Whenitreacheszero thesystemissuesa soft alarm thenexttimetheunitisswitchedon Thealarmonlymakesthealarmmenusymbolflash notthe redalarmindicator and TIMEFORSERVICE isshowninthedisplay Thealarmwillnotmaketheunit stop Theunitcanstillbeoperatedasnormalwiththealarmpresent Followthesestepstochecktheserviceparametersandstoptheserviceal...

Страница 26: ...fX Rst NO 3 Toggle NO to YES by pressing either or 4 Confirmby pressing Allvaluesrevertstofactorysettings 6 14 Accesslevels Thefollowingaccesslevelsandactionsareavailableinthecontrolsystem Accesslevel Availableactions Comment ACCESS Viewallprocessingdata ACCESS Viewallprocessingdata Adjustrelevantparameters fanspeed set valueRH reseth orkWhetc ACCESS Level2 isfordedicatedpersonnelonly qualifiedper...

Страница 27: ...willstarttodehumidifyagain whenthehumidityisequalto orgreaterthantheSetValue Typeofhumiditycontrol relativehumidity dewpointorabsolutehumidity andunitsystem metricor imperial governsthereadingsandsettingsinthismenu See7 5 Functionsforreferenceandexplanation ThistableshowsthedisplayviewsandpossiblesettingsoftheHumiditymenu Displayview Description Type Settingoption C fX kWh fX RH1 49 Internal senso...

Страница 28: ...ywillautomaticallybedesignated RH2 D2 X2 and RH3 D3 X3 bythesystem numbertwobeingthefirstconnectedinthechain Whenconnected itispossibletochooseoneoftheexternalsensorsascontrol Thedisplaywillthenshow RH D X2 or RH D X3 Withanexternalsensorsetascontrolsensor itispossibletodisconnectandreconnecttheexternal sensor swithoutlosingthecontrolsetting e g RH2 whiletheunitisswitchedoff butpowered Whenswitche...

Страница 29: ... ThistableshowsthedisplayviewsandtypeofinformationoftheTimemenu Displayview Description Type Settingoption fX kWh fX 261 h C C Run timetripmeter RESETTABLE Yes No fX kWh fX 341 h C C Totalruntime Displayjumps from TOTAL to display view and back READONLY fX kWh fX S 3999 h C C Timeto service RESETTABLE Yes No fX kWh fX T 4000 h C C Serviceinterval ADJUSTABLE Every100 hours Table7 2Timemenu 190TEN 1...

Страница 30: ...Power W current A andvoltage V measurementsinthismenu NOTE Resetting is always performedmanually Unplugging the unit ora power failure will not reset the kWh counter ThistableshowsthedisplayviewsandtypeofinformationofthePowermenu Displayview Description Type Settingoption fX kWh fX 411 kWh C C kWh kWhcounter RESETTABLE Yes No fX kWh fX 887 W C C kWh Real timePower READONLY fX kWh fX 3 88 229 C C R...

Страница 31: ...nlettemperature T1 ismeasured NOTE Thetemperature will be shown in Celsius metric SI orFahrenheit imperial IP depending onthe units setting in the Functions menu ThistableshowsthedisplayviewsandtypeofinformationoftheTemperaturemenu Displayview Description Type Settingoption fX kWh fX T1 28 C C C Processairinlet temperature internal sensor READONLY fX kWh fX T2 23 C C C Externalsensor 1 READONLY fX...

Страница 32: ...on Type Settingoption fX kWh fX Wt 39 C C C Wet airtemperature READONLY fX kWh fX Ri 31 C C C Reactivation inlet temperature READONLY 1 Only if externalsensor isconnected Table7 4Temperaturemenu 29 Menusandparameters 190TEN 1098 D1404 ...

Страница 33: ... ThisisrepeateduntilthehumidityreachestheSetValue whichwillmakethe dehumidificationstartagain FanDEM on DEMand In FanDEM onDEMand mode thefanwillstopwhenthedesiredhumidity SetValueminus Hysteresis isreached It willstartagainwhenthesensedhumidityisequalto orgreaterthantheSet Value Thisgivesinpracticea controlwithgreaterhysteresisthan FanINT dependingon thefollowing Whenthedehumidifierhas reachedthe...

Страница 34: ...ocessfan speed ADJUSTABLE SpdHIGH NORM LOW fX kWh fX FAN ON C C Processfan running modes ADJUSTABLE Fan ON INT DEM fX kWh fX SI C C Metricorimperialunits ADJUSTABLE SI IP fX kWh fX RH C C Humidity ADJUSTABLE RH Dp Absolute humidity fX kWh fX ID999999 C C Unit serial no READONLY IDno fX kWh fX ACCESS C C ACCESSLevel ADJUSTABLE ACCESS 31 Menusandparameters 190TEN 1098 D1404 ...

Страница 35: ...pe Settingoption fX kWh fX Default C C Restoreto default settings onlypossible when dehumidifierisOFF RESETTABLE Yes orNo fX kWh fX 50Hz C C Mainsfrequency ADJUSTABLE 50 or60 Hz Table7 5Functionsmenu 190TEN 1098 D1404 Menusandparameters 32 ...

Страница 36: ...takeacoupleofminutes CA CA CAUTION UTION UTION Do not unplug the dehumidifier while it is cooling down the underlying reason forthe alarmmight beoverheating ThistableshowsthedisplayviewsandtypeofinformationoftheAlarmmenu Displayview Description Type fX kWh fX HEATER C C Sourceof alarmin fulltext RESETTABLE fX kWh fX No Alarm C C Alarmstatus READONLY Table7 6Alarm menu 33 Menusandparameters 190TEN ...

Страница 37: ...tyvalues 7 7 2 Servicetime Thistableshowstheminimum maximumanddefaultservicetimevalues Parameter Defaultsetting Max Min T 4000h servicetime 4000 8000 500 Table7 8Time min maxanddefaultservicetimevalues 7 7 3 Functions ThistableshowsthedefaultsettingsandsettingoptionsoftheFunctionsmenu Parameter Defaultsetting Options SpdNORM SpdNORM SpdHIGH SpdLOW FanON FanON FanINT FanDEM SI unit SI metricunits I...

Страница 38: ...nand maintenanceproceduresaswellastherecommendedintervalsforunitsusedundernormaloperatingand environmentalconditions Iftheprocessaircontainsalotofdust preventativemaintenanceshouldbe performedatshorterintervalsthanthosespecifiedbelow Inspection maintenance Component 4000hours 6months 8000 hours 12months Processfilter Clean the filtercartridge Cleanthe filterhousing and replacethe filterif necessar...

Страница 39: ...filterchange 1 Push the filterframe down Figure8 1 2 Pullthe filterholder outwards and remove it fromthe unit Figure8 2 3 Remove the old filter 4 Replace it with a new filter Figure8 3 190TEN 1098 D1404 Serviceandmaintenance 36 ...

Страница 40: ...topped Thendisconnect the power supply Check that the filters hosesorducts arenot clogged To resetthe overtemperatureprotectionfuse the unitmust be disconnected fromthe mains and allowed to cool down If the alarmisreissuedafterthe unithascooleddown and the alarmhasbeenreset contactMunters SetValueRH istoo low in dry environment Check if low SetValueRHis necessary Adjustto higher value Alarmmessage...

Страница 41: ...the measuredhumidity Loss of performance The dehumidifier isrunning but is not controlling the humidity Low reactivationairflow Check the filterand anyhoses orductsforleakageor blockage Theuseof a restrictingflange incombination with wall pipescancause too little reactivationairflow Table9 1Faulttracinglist 190TEN 1098 D1404 Faulttracing 38 ...

Страница 42: ...igure10 1Dimensions ComDryM160L 1 Processairinlet 2 Dryairoutlet 3 Coolingair Width A Width B Height C Diameter Dryair Diameter Drainhose Service space F Service space G Weight 445 mm 270 mm 555 mm 100 mm 12 5mm 350 mm 500 mm 17 kg Table10 1Dimensionsandweight 39 Technicalspecification 190TEN 1098 D1404 ...

Страница 43: ...ture processair C 2 Relative Humidity processair RH 3 Dehumidificationcapacity kg h moistureremoval kg hour 10 3 Fancurveprocessair ComD ry M160L High speed 0 20 40 60 80 100 120 140 160 180 200 220 240 B m h A Pa 0 25 50 75 100 125 150 175 200 Figure10 3Fancurve Density 1 2 kg m3 A Staticpressure Pa B Airflow m3 hour 190TEN 1098 D1404 Technicalspecification 40 ...

Страница 44: ...g processfan dBA 67 Electricalprotectionclass casing IP33 Electricalprotectionclass electricpanel IP54 Fan MotorWinding Insulation Class Class B DriveMotorWinding Insulation Class Class B Rotortype HPS AirfilterG3 articlenumber 150 012054 001 Environmentalconditions Operatingtemperature C 0 30 Maximuminstallation altitude above sealevel m 2000 Transportand storage temperature C 20 70 Totalpower vo...

Страница 45: ...sbeenexposedtochemicalsthataredangeroustotheenvironmenttheriskmustbeassessed Thechemicalscanaccumulateintherotormaterial Takethenecessaryprecautionstocomplywith applicablelegalrequirementsandregulations W W WARNING ARNING ARNING If the rotoris to becut in pieces wear a suitable CEmarked face mask selected and fitted in accordance with the applicable safety standards to protect fromthe dust 190TEN ...

Страница 46: ......

Страница 47: ...heersing munters nl www munters nl POLAND Munters Sp z o o Oddzial w Polsce AirTreatment ul Swietojanska 55 11 81 391 Gdynia Tel 48 58 305 35 17 dh munters pl www munters com pl SPAIN Munters Spain SA AirTreatment EuropaEpresarial Edificio Londres C Playa de Liencres 2 28230 Las Matas Madrid Tel 34 91 640 09 02 marketing munters es www munters es SWEDEN Munters Europe AB AirTreatment P O Box 1150 ...

Страница 48: ...www munters com ...

Отзывы: