ComDry M160L
7.7 Min, max and default values
7.7.1 Humidity
This table shows the minimum, maximum and default humidity values:
Parameter
RH (%)
Dp (°C)
X (gr/kg)
Dp (°F)
X (grain/lb)
Max.
95
40
40
99
300
Default
50
9
7,3
49
51
SV_RH 50%
(set value)
Min.
5
-30
0,5
-20
2
Max.
10
10
1,0
10
10
Default
2
2
0,2
2
2
HYS 2%
(hysteresis)
Min.
0
0
0,0
0
0
Table 7.7 Minimum, maximum and default humidity values
7.7.2 Service time
This table shows the minimum, maximum and default service time values:
Parameter
Default setting
Max.
Min.
T- 4000 h (service time)
4000
8000
500
Table 7.8 Time, min/max and default service time values
7.7.3 Functions
This table shows the default settings and setting options of the Functions menu:
Parameter
Default setting
Options
Spd NORM
Spd NORM
Spd HIGH, Spd LOW
Fan ON
Fan ON
Fan INT, Fan DEM
SI (unit)
SI (metric units)
IP (imperial units)
Dp (°C / °F)
RH (%)
RH (%)
X (gr/kg) / (grain/lb)
Table 7.9 Default settings and setting options of the Functions menu