background image

3

1.0 Chiller Identification

The module information data plate is located inside the electrical box compartment of each module. When ordering service parts or inquiring for technical 
assistance it is important to provide the model and serial number.

1.1 Water Cooled Model Number

ASP15X2H2A0-410a

ASP   15  

X  

2  

H  

2  

 -410a

ASP = Air Stack Packaged

15 = tons (10,15,20,30,60, -tons)

X or C = X: Copeland 410a Compressor  

C : Trane Scroll  

2 or 1 = 1: Dual Circuit Evaporator, 1: Single Circuit Evaporator

H = 460V  

(Or: A = 208V  

L = 230V  

C = 575V  

V = special)

2 = Multiple Module Power 

1 = Direct Connect Power

A = Water Cooled (Or: 

D = DX unit,  R= Heat Pump, F= Free Cool, C=Condenser, L=Fluid Cooler)

O = ARI Version

410a = Refrigerant

1.2 Serial Number Identification

AJ-06-25

A = Decade built  

I = 1990’s  

J= 2000’s 

A=2010’s

J = Year built  

A= ’01, B= ’02, C=’03…J=’10

06 = June (month built)  

01 = Jan.  

02 = Feb. 

25 = 25th module built  

01 = 1st  

02 = 2nd 

2.0 Theory of Operation

The Airstack ASPX chillers provide chilled water to an external load based off of the return water temperature calculated on the module Master Control.  When 
the Entering Chilled Water sensor sends the signal to the Master Control that Cooling is needed, compressors will begin to start and produce Chilled Water.  The 
point at which the Entering Chilled Water temperature calls for compressors to start is determined by the Up - Setpoint, Lo-Setpoint and the Variable Setpoint 
settings in the System Variables menu of the Master Control.

When the ECHW sensor is signaled that Chilled Water temperature has dropped below the set-point, compressors will begin to cycle off.

3.0 Water Treatment

Proper water treatment is essential to ensure the peak efficiency and performance of the Chiller.  The evaporator side water quality should be kept within 
the following parameters to prevent any damage to the heat exchangers.  The use of hydrochloric, sulfuric, and muriatic acids as well as household bleach 
can cause stress corrosion to the stainless steel in the heat exchangers.  Use of these or any other unapproved chemicals is not covered under the Multistack 
warranty.

 Multistack 

Water 

Guidelines

 

PH 

> 7  -  < 9

 

TDS 

< 1000 ppm  (if glycol used this parameter will be exceeded)

 

Hardness 

30 - 500 ppm

 

Alkalinity 

30 - 500 ppm  (if glycol used this parameter will be exceeded)

 

Chlorides 

< 200 ppm

 

Sulphates 

< 200 ppm

Содержание Airstack ASPX Series

Страница 1: ...ASP X Chiller Modules Operation and Maintenance Manual...

Страница 2: ...or Oil Level 8 13 0 Refrigerant Charge Evacuation 8 14 0 Filter Driers 8 15 0 Condenser Fan Control 8 16 0 Superheat Subcooling 8 17 0 Pressure Relief Valve 9 18 0 Annual Maintenance 9 19 0 Compressor...

Страница 3: ...hemoduleMasterControl When theEnteringChilledWatersensorsendsthesignaltotheMasterControlthatCoolingisneeded compressorswillbegintostartandproduceChilledWater The pointatwhichtheEnteringChilledWatertem...

Страница 4: ...tageimbalance It is very important to keep the unbalance between electrical phases to a minimum There will always be one module in the bank that is the Master Module This module contains the Master Co...

Страница 5: ...e Master Module has and Entering Chilled Water Sensor A System Leaving ChilledWater Sensor is shipped in the electrical panel of the Master Module and should be field installed 2 10 after the first mo...

Страница 6: ...ver ChillerModulesuseamechanicalexpansionvalveforrefrigerantcontroltotheevaporator Superheatshouldbesettoapproximately10 12 F TheLiquidLine Solenoid is used to prevent refrigerant migration into the e...

Страница 7: ...age of this manual is an information log sheet for the chiller The log sheet can be used daily weekly or as desired to record operation characteristics of the chiller The information recorded on the l...

Страница 8: ...level should be maintained at 1 8 full To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors Factory oil charge volume for each comp...

Страница 9: ...L stainless steel and copper Do not use bleach or hydrochloric or sulfuric acids 18 4 Condenser Coils The condenser side coils should be cleaned periodically of air born debris to maximize efficiency...

Страница 10: ...tothecompressoritisrecommendedthecompressorbereplacedasremovingallthemoisture from the oil is very difficult Replacement of the condenser side heat exchanger the expansion valve and installation of a...

Страница 11: ...icalmodulethroughthebottomheadersothemechanicalmodulebottomheader will connect with the free cool module bottom header Leaving chilled water can the either exit the chiller through the free cool modul...

Страница 12: ...ebottomofthetankandpouritbackintothetankinadifferentlocationmixing the solution PressureGauge Thepressuregaugeshowsthepressurethatthechilledwaterloopisoperatingat ItisalsoshowingwhatthePressureRegulat...

Страница 13: ...mode On a normal application without water valves if you have 10 compressors and flow at a true 10 F DeltaT with setpoints of 55 Up and 45 Lo andVSP at 50 your no load point would be 50 F The last mo...

Страница 14: ...setpoints in system variables Check for flow restriction No Demand Check entering ECHW sensor Check setpoints in system variables Check sensor location 100 Demand all the time Check entering CHW senso...

Страница 15: ...Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 Ent Chw Lvg Chw Demand Capacity System Upset Loset VSP Load Limit Tdiff Index Sy...

Страница 16: ...F162ASP O M 072610 1064 Maple Avenue Sparta WI P 608 366 2400 F 608 366 2450 www multistack com...

Отзывы: