background image

10

20.0  Heat Exchangers

Multistack uses brazed plate stainless steel heat exchangers on the evaporator side of our modules. These heat exchangers are made of 316L stainless steel 
and 99.9% pure copper.  Condenser side heat exchangers are made from direct expansion copper tube and aluminum fin.  Without proper water treatment 
or due to abuse, the evaporator side heat exchangers can corrode and eventually develop an internal leak.  In such an event it would become necessary to 
replace the heat exchanger.

Following are the steps for field replacement of a failed evaporator side heat exchanger.

1. If the refrigerant has not been lost on the failed circuit, you should first  do a standard refrigerant recovery.
2. Begin by isolating the module and draining the water/glycol from the loop.
3.  Remove the 4- 8” round header pipes that attach to brazed plate heat exchanger (if you have a front module).  For rear module(s), remove the crossover 

pipes from the front module.

4. Cut the refrigerant lines below the elbows and sweat off remaining pipe.
5. Remove old heat exchanger and replace with new one.
6. Fit in copper connections and braze.  Purge with Nitrogen while brazing.
7. After brazing, do a leak check and evacuate to a maximum of 500 microns.  Charge the circuit according to the name plate specification.

If the brazed plate heat exchanger failure has caused water to enter into the refrigerant side, the compressor and condenser side heat exchanger should also 
be checked for possible contamination.  If water has entered into the compressor it is recommended the compressor be replaced as removing all the moisture 
from the oil is very difficult.  Replacement of the condenser side heat exchanger, the expansion valve, and installation of a liquid line filter drier with a water 
core cartridge is also recommended.  Evacuate the circuit to a maximum of 500 microns and let stand for 20 minutes.  Charge the circuit, and run two-to-three 
weeks with the high water core cartridge, and then replace with a standard core.

The condenser side heat exchangers on ASPX modules require periodic cleaning of the fins to keep airborne debris from plugging up the fins and causing high 
pressure conditions.  A coil cleaner suitable for copper and aluminum can be used for this.

21.0  Optional Low Ambient Package

The standard operating range for ASPX modules is 95°F through 20°F.  For operation from 20°F to negative 20°F modules should be ordered with the Low 
Ambient Package.  This includes the flooded head pressure control valve, properly sized liquid receiver tank to handle both summer and winter charge, liquid 
line check valve, and setting the chiller into the Low Ambient or Low Temperature mode.  Note on modules large than 15 tons, two head pressure control 
valves will be used in parallel.  When doing low ambient applications it is also suggested to use VFDs for condenser fan control. 

22.0 Optional Pump Modules

To provide water flow to the chiller bank, Pump Modules can be provided in various sizes and 
configurations to connect directly to the mechanical or free cooling modules.  The standard pump 
would be built in the same frame size as the cooling modules and come with a Series 4382 dual arm 
with 1 primary pump and the 2nd as back up.  Pumps can be manually rotated for equal run time or 
special ordered with auto lead lag capability.

Содержание Airstack ASPX Series

Страница 1: ...ASP X Chiller Modules Operation and Maintenance Manual...

Страница 2: ...or Oil Level 8 13 0 Refrigerant Charge Evacuation 8 14 0 Filter Driers 8 15 0 Condenser Fan Control 8 16 0 Superheat Subcooling 8 17 0 Pressure Relief Valve 9 18 0 Annual Maintenance 9 19 0 Compressor...

Страница 3: ...hemoduleMasterControl When theEnteringChilledWatersensorsendsthesignaltotheMasterControlthatCoolingisneeded compressorswillbegintostartandproduceChilledWater The pointatwhichtheEnteringChilledWatertem...

Страница 4: ...tageimbalance It is very important to keep the unbalance between electrical phases to a minimum There will always be one module in the bank that is the Master Module This module contains the Master Co...

Страница 5: ...e Master Module has and Entering Chilled Water Sensor A System Leaving ChilledWater Sensor is shipped in the electrical panel of the Master Module and should be field installed 2 10 after the first mo...

Страница 6: ...ver ChillerModulesuseamechanicalexpansionvalveforrefrigerantcontroltotheevaporator Superheatshouldbesettoapproximately10 12 F TheLiquidLine Solenoid is used to prevent refrigerant migration into the e...

Страница 7: ...age of this manual is an information log sheet for the chiller The log sheet can be used daily weekly or as desired to record operation characteristics of the chiller The information recorded on the l...

Страница 8: ...level should be maintained at 1 8 full To ensure no liquid is present in the oil the crankcase heaters should be on 24 hours before starting of the compressors Factory oil charge volume for each comp...

Страница 9: ...L stainless steel and copper Do not use bleach or hydrochloric or sulfuric acids 18 4 Condenser Coils The condenser side coils should be cleaned periodically of air born debris to maximize efficiency...

Страница 10: ...tothecompressoritisrecommendedthecompressorbereplacedasremovingallthemoisture from the oil is very difficult Replacement of the condenser side heat exchanger the expansion valve and installation of a...

Страница 11: ...icalmodulethroughthebottomheadersothemechanicalmodulebottomheader will connect with the free cool module bottom header Leaving chilled water can the either exit the chiller through the free cool modul...

Страница 12: ...ebottomofthetankandpouritbackintothetankinadifferentlocationmixing the solution PressureGauge Thepressuregaugeshowsthepressurethatthechilledwaterloopisoperatingat ItisalsoshowingwhatthePressureRegulat...

Страница 13: ...mode On a normal application without water valves if you have 10 compressors and flow at a true 10 F DeltaT with setpoints of 55 Up and 45 Lo andVSP at 50 your no load point would be 50 F The last mo...

Страница 14: ...setpoints in system variables Check for flow restriction No Demand Check entering ECHW sensor Check setpoints in system variables Check sensor location 100 Demand all the time Check entering CHW senso...

Страница 15: ...Suct Temp LoChwTemp Fault if any Comp 1 Comp 2 Comp 3 Comp 4 Comp 5 Comp 6 Comp 7 Comp 8 Comp 9 Comp 10 Comp 11 Comp 12 Ent Chw Lvg Chw Demand Capacity System Upset Loset VSP Load Limit Tdiff Index Sy...

Страница 16: ...F162ASP O M 072610 1064 Maple Avenue Sparta WI P 608 366 2400 F 608 366 2450 www multistack com...

Отзывы: