581 – AL Wiring PWM_CM3
Red alarm.
Associated parameter 1.1041.923
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM3.
u
Check setting at engine governor.
583 – AL GLS closed
Red alarm. Engine shutdown.
Associated parameter 2.0451.115
Cause
Corrective action
Generator load switch does not
open when engine stops. Engine
is motoring.
1. Check generator load switch.
2. Manually disconnect generator switch.
3. Open any existing mains circuit breaker.
4. Where possible, do not operate manual emergency stop.
587 – AL Wiring PWM_CM4
Red alarm.
Associated parameter 1.1041.924
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM4.
u
Check setting at engine governor.
596 – AL Develop PR Set
Red alarm.
Associated parameter 1.8004.645
Cause
Corrective action
The ECU parameter record in use
is a test version.
u
Load series parameter record on ECU.
597 – AL Wiring PWM_CM5
Red alarm.
Associated parameter 1.1041.925
Cause
Corrective action
Wire break or short circuit on
channel PWM_CM5.
u
Check setting at engine governor.
603 – SD Air Humidity
Yellow alarm.
Associated parameter 1.0165.900
Cause
Corrective action
Air humidity sensor faulty. Short
circuit or wire break.
u
Check cabling and sensor (→ Page 202).