1.4540.055 – Factory CAL Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
Hardware not ready for operation.
1. Restart TecJet.
2. Replace TecJet.
1.4540.056 – PWM Duty Cycle High Error
Red alarm. Initiated by TecJet.
Cause
Corrective action
TecJet setting is not correct.
u
Check TecJet setting.
1.4550.031 – A - Internal Fault
Red alarm. Initiated by throttle of cylinder bank A.
Cause
Corrective action
Hardware not ready for operation.
1. Restart throttle.
2. Replace throttle.
1.4550.032 – A - Stop commanded (Run/Stop)
Yellow alarm. Initiated by throttle of cylinder bank A.
Cause
Corrective action
Throttle setting is not correct.
u
Check throttle setting.
1.4550.033 – A - Input (Supply) Voltage Fault
Yellow alarm. Initiated by throttle of cylinder bank A.
Cause
Corrective action
Supply voltage has reached
maximum or minimum limit value.
1. Check supply voltage.
2. Check cabling (→ Page 202).
1.4550.034 – A - Position Error
Red alarm. Initiated by throttle of cylinder bank A.
Cause
Corrective action
Position specification and
feedback signal do not match .
1. Check mechanical system.
2. Restart throttle.
1.4550.035 – A - Temperature Sensor Fault
Red alarm. Initiated by ProAct of cylinder bank A.
Cause
Corrective action
Internal temperature sensor
faulty.
1. Restart throttle.
2. Replace throttle.