6.2 Fault indication on printed circuit board SAM
The structure of the display (1) is as follows:
• First line
• Fault indication
• # (2) = Alarm is no longer active, does not appear on next power-up,
• A = Currently active alarms,
• B = Alarm was active during the last hour,
• C = Alarm was active during the last four hours,
• C = Alarm was active during the last four to twelve hours,
• E = Alarm was active more than twelve hours ago.
.
• Fault type (e.g. SE03).
• Node number at which the fault occurred (e.g. nd11).
• Second line
• Running text, providing more information about the fault currently displayed
Proceed to the next alarm by pressing key (↓ ↑).
Fault type – fault message text
SE No.
Fault message text
0
Sensor Temperature Defect
1
Temperature failure
2
Sensor Voltage Defect
3
Voltage failure
4
CAN Bus- 1 Error/Bus Defec
5
CAN Bus- 1 Overrun
6
CAN Bus- 2 Error/Bus Defec
7
CAN Bus- 2 Overrun
8
Temperature Compensation Error
9
I/O-Module Slot2 Defect
10
I/O-Module Slot3 Defect
64 | Troubleshooting | MS150025/02E 2012-10
TIM-ID: 0000008959 - 001